FireCADCalc

Fabric Heat Loss with Linear and Point Thermal Bridges

Envelope heat transfer coefficient from U × A plus linear (ψ × length) and point (χ) thermal bridges, with the bridges' share and heat loss.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 200 m² wall with reveals and junctionsWell insulated 0.15 W/m²K, balcony slabs

Results

ψ-values from numerical calculation (ISO 10211) or catalogues of details; in well-insulated buildings bridges often add 10–30 % to fabric loss.

Plane element coefficient0.045000kW/K
Thermal bridge coefficient0.019800kW/K
Share of thermal bridges30.556%
Heat loss1,944.0W

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 200 m² wall with reveals and junctions. The inputs, in the units selected above:

InputValue
Plane element U-value0.30000 W/(m²·K)
Plane element area200.00 m²
Linear bridge 1, ψ-value (per metre of junction)0.10000 W/(m·K)
Length of bridge 160.000 m
Linear bridge 2, ψ-value (per metre of junction)0.050000 W/(m·K)
Length of bridge 240.000 m
Point bridge (each)1.0000e-04 kW/K
Number of point bridges20.000 -
Inside–outside temperature difference25.000 K

Applying the formula below gives:

ResultValue
Plane element coefficient0.060000 kW/K
Thermal bridge coefficient0.010000 kW/K
Share of thermal bridges14.286 %
Heat loss1,750.0 W

Open this example in the calculator and change any input.

Formula

\(H = UA + \sum\psi_jl_j + \sum\chi_k, \quad Q = H\Delta T\)

Variables

Symbol Meaning SI unit
\(U\) Plane element U-value W/(m²·K)
\(A\) Plane element area m²
\(\psi_1\) Linear bridge 1, ψ-value (per metre of junction) W/(m·K)
\(l_1\) Length of bridge 1 m
\(\psi_2\) Linear bridge 2, ψ-value (per metre of junction) W/(m·K)
\(l_2\) Length of bridge 2 m
\(\chi\) Point bridge (each) W/K
\(n_\chi\) Number of point bridges -
\(\Delta T\) Inside–outside temperature difference K
\(H_U\) Plane element coefficient W/K
\(H_{TB}\) Thermal bridge coefficient W/K
\(H_{TB}/H\) Share of thermal bridges -
\(Q\) Heat loss W

Method and standards

ISO 13789 transmission coefficient.

Where it is used

  • Envelope heat loss with junctions.
  • Comparing construction details.

Common mistakes

  • Leaving bridges out of loss calculations.
  • Double counting with internal dimensions.

Assumptions and limits

  • A ψ-value has the units of thermal conductivity, W/(m·K) (Btu/(h·ft·°F) in FPS), but means heat flow per metre of junction per kelvin; the page converts it as such.

  • Steady state.

References

  • H = ΣUA + Σψl + Σχ (ISO 14683 / ISO 13789 method)

Questions and answers

What is a ψ-value?

Extra heat flow per metre of a junction (wall–floor, window reveal, balcony) beyond what the plane U-values account for.

Why do bridges matter more in insulated buildings?

The plane elements lose little, so junctions become a large share; they also cause cold spots and mould.

What do the defaults represent?

A 200 m² wall with window-reveal and floor-junction bridges and some wall-tie point bridges.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.