Worked example
Example: 200 m² wall with reveals and junctions. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Plane element U-value | 0.30000 W/(m²·K) |
| Plane element area | 200.00 m² |
| Linear bridge 1, ψ-value (per metre of junction) | 0.10000 W/(m·K) |
| Length of bridge 1 | 60.000 m |
| Linear bridge 2, ψ-value (per metre of junction) | 0.050000 W/(m·K) |
| Length of bridge 2 | 40.000 m |
| Point bridge (each) | 1.0000e-04 kW/K |
| Number of point bridges | 20.000 - |
| Inside–outside temperature difference | 25.000 K |
Applying the formula below gives:
| Result | Value |
|---|---|
| Plane element coefficient | 0.060000 kW/K |
| Thermal bridge coefficient | 0.010000 kW/K |
| Share of thermal bridges | 14.286 % |
| Heat loss | 1,750.0 W |
Open this example in the calculator and change any input.
Formula
\(H = UA + \sum\psi_jl_j + \sum\chi_k, \quad Q = H\Delta T\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(U\) | Plane element U-value | W/(m²·K) |
| \(A\) | Plane element area | m² |
| \(\psi_1\) | Linear bridge 1, ψ-value (per metre of junction) | W/(m·K) |
| \(l_1\) | Length of bridge 1 | m |
| \(\psi_2\) | Linear bridge 2, ψ-value (per metre of junction) | W/(m·K) |
| \(l_2\) | Length of bridge 2 | m |
| \(\chi\) | Point bridge (each) | W/K |
| \(n_\chi\) | Number of point bridges | - |
| \(\Delta T\) | Inside–outside temperature difference | K |
| \(H_U\) | Plane element coefficient | W/K |
| \(H_{TB}\) | Thermal bridge coefficient | W/K |
| \(H_{TB}/H\) | Share of thermal bridges | - |
| \(Q\) | Heat loss | W |
Method and standards
ISO 13789 transmission coefficient.
Where it is used
- Envelope heat loss with junctions.
- Comparing construction details.
Common mistakes
- Leaving bridges out of loss calculations.
- Double counting with internal dimensions.
Assumptions and limits
A ψ-value has the units of thermal conductivity, W/(m·K) (Btu/(h·ft·°F) in FPS), but means heat flow per metre of junction per kelvin; the page converts it as such.
Steady state.
References
- H = ΣUA + Σψl + Σχ (ISO 14683 / ISO 13789 method)
Questions and answers
What is a ψ-value?
Extra heat flow per metre of a junction (wall–floor, window reveal, balcony) beyond what the plane U-values account for.
Why do bridges matter more in insulated buildings?
The plane elements lose little, so junctions become a large share; they also cause cold spots and mould.
What do the defaults represent?
A 200 m² wall with window-reveal and floor-junction bridges and some wall-tie point bridges.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.