Natural Ventilation by Stack Effect

Natural (stack) ventilation flow through low and high openings from the height between them and the indoor–outdoor temperature difference.

Inputs

Examples: Turbine hall, 15 mUnequal openings, winter

1.2 kg/m³ at about 20 °C; 1.13 at 40 °C. Used only for the heat removed.

Results

Wind adds to or works against the stack; the stack value is what you get on a still day.

Effective area (openings in series)2.8284m²
Stack flow19,038m³/h
Heat removed ρ c_p V ΔT (c_p 1006 J/(kg·K))63.841kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Turbine hall, 15 m. The inputs, in the units selected above:

InputValue
Free area of the low openings4.0000 m²
Free area of the high openings4.0000 m²
Height between opening centres15.000 m
Indoor temperature40.000 °C
Outdoor temperature30.000 °C
Discharge coefficient0.61000 -
Air density for the heat removed1.2000 kg/m³

Applying the formula below gives:

ResultValue
Effective area (openings in series)2.8284 m²
Stack flow19,038 m³/h
Heat removed ρ c_p V ΔT (c_p 1006 J/(kg·K))63.841 kW

Open this example in the calculator and change any input.

Formula

\(\dot V = C_d A_e\sqrt{\frac{2 g H |T_i - T_o|}{T_w}}, \quad T_w = \max(T_i, T_o), \quad \frac{1}{A_e^2} = \frac{1}{A_1^2} + \frac{1}{A_2^2}, \quad \dot Q = \rho c_p \dot V |T_i - T_o|\)

Variables

Symbol Meaning SI unit
\(A_1\) Free area of the low openings m²
\(A_2\) Free area of the high openings m²
\(H\) Height between opening centres m
\(T_i\) Indoor temperature K
\(T_o\) Outdoor temperature K
\(C_d\) Discharge coefficient -
\(A_e\) Effective area (openings in series) m²
\(\dot V\) Stack flow m³/s
\(\dot Q\) Heat removed ρ c_p V ΔT (c_p 1006 J/(kg·K)) W
\(\rho\) Air density for the heat removed kg/m³
\(c_p\) Specific heat of air, 1 006 J/(kg·K)
\(T_w\) The warmer of T_i and T_o (absolute) K
\(g\) Standard gravity, 9.806 65 m/s²

Method and standards

Bernoulli with buoyancy.

Where it is used

  • Turbine halls, boiler houses and warehouses.
  • Smoke and heat vents.

Common mistakes

  • Gross instead of free area.
  • Ignoring wind.

Assumptions and limits

  • Still air, well-mixed interior.
  • The buoyancy term divides by the warmer absolute temperature, so the same formula holds when the inside is colder than outside (flow reversed).
  • The air density for the heat removed is an input (default 1.2 kg/m³); use the density at the outlet air temperature, about 1.13 kg/m³ at 40 °C.

References

  • Buoyancy-driven flow Q = C_d A_e √(2gHΔT/T)
  • openings in series 1/A_e² = 1/A₁² + 1/A₂² (CIBSE AM10; ASHRAE Handbook—Fundamentals ch. 16)

Questions and answers

4 m² low and high, 15 m apart, 40 °C inside, 30 °C out?

About 5.3 m³/s (19,000 m³/h), removing some 64 kW.

Why combine the areas?

Air must pass both; the smaller one controls.

Turbine halls?

Tall halls with roof monitors rely on this.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.