Kitchen Hood Exhaust Air Flow

Exhaust air flow for a kitchen or process hood from its length and a flow per metre, or from the open face area and capture velocity, whichever is larger.

Inputs

Examples: 3 m canopyDeep wall canopy, face governs

From your hood guide for the cooking duty and hood type.

Results

Make-up air below the exhaust keeps the kitchen slightly negative so smells do not escape.

By length1,728.0m³/h
By face area and velocity3,888.0m³/h
Exhaust (larger)3,888.0m³/h
Make-up air3,499.2m³/h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 3 m canopy. The inputs, in the units selected above:

InputValue
Hood length3.0000 m
Exhaust per metre of hood300.00 L/(s·m)
Hood depth (open face)1.2000 m
Capture velocity across the open face0.25000 m/s
Make-up air share of exhaust85.000 %

Applying the formula below gives:

ResultValue
By length3,240.0 m³/h
By face area and velocity3,240.0 m³/h
Exhaust (larger)3,240.0 m³/h
Make-up air2,754.0 m³/h

Open this example in the calculator and change any input.

Formula

\(\dot V = \max(L q_L,\ L W v_c)\)

Variables

Symbol Meaning SI unit
\(L\) Hood length m
\(q_L\) Exhaust per metre of hood m³/(s·m)
\(W\) Hood depth (open face) m
\(v_c\) Capture velocity across the open face m/s
\(k_m\) Make-up air share of exhaust -
\(\dot V_L\) By length m³/s
\(\dot V_A\) By face area and velocity m³/s
\(\dot V\) Exhaust (larger) m³/s
\(\dot V_m\) Make-up air m³/s

Method and standards

Flow rules.

Where it is used

  • Plant canteens and process hoods.
  • Exhaust fan selection.

Common mistakes

  • Only one method checked.
  • No make-up air.

Assumptions and limits

  • Wall canopy hood (face area L × W). An island hood is open on all sides: use its perimeter-based rate from the code or maker; the face rule here understates it.
  • The default rates are illustrative, not from a standard: enter your code's or the maker's figures for the appliance duty.

References

  • Q = L q_L or Q = A v_c (hood design practice with the user's rates from the applicable code or the hood maker, e.g. ASHRAE Standard 154)

Questions and answers

3 m hood, 1.2 m deep, 0.3 m³/s per metre or 0.25 m/s?

0.9 m³/s by length, 0.9 m³/s by face: 3,240 m³/h.

Why make-up air?

Without it doors whistle and the hood cannot exhaust its design flow.

Grease filters?

Add their pressure drop to the fan selection.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.