Worked example
Example: 3 m canopy. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Hood length | 3.0000 m |
| Exhaust per metre of hood | 300.00 L/(s·m) |
| Hood depth (open face) | 1.2000 m |
| Capture velocity across the open face | 0.25000 m/s |
| Make-up air share of exhaust | 85.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| By length | 3,240.0 m³/h |
| By face area and velocity | 3,240.0 m³/h |
| Exhaust (larger) | 3,240.0 m³/h |
| Make-up air | 2,754.0 m³/h |
Open this example in the calculator and change any input.
Formula
\(\dot V = \max(L q_L,\ L W v_c)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(L\) | Hood length | m |
| \(q_L\) | Exhaust per metre of hood | m³/(s·m) |
| \(W\) | Hood depth (open face) | m |
| \(v_c\) | Capture velocity across the open face | m/s |
| \(k_m\) | Make-up air share of exhaust | - |
| \(\dot V_L\) | By length | m³/s |
| \(\dot V_A\) | By face area and velocity | m³/s |
| \(\dot V\) | Exhaust (larger) | m³/s |
| \(\dot V_m\) | Make-up air | m³/s |
Method and standards
Flow rules.
Where it is used
- Plant canteens and process hoods.
- Exhaust fan selection.
Common mistakes
- Only one method checked.
- No make-up air.
Assumptions and limits
- Wall canopy hood (face area L × W). An island hood is open on all sides: use its perimeter-based rate from the code or maker; the face rule here understates it.
- The default rates are illustrative, not from a standard: enter your code's or the maker's figures for the appliance duty.
References
- Q = L q_L or Q = A v_c (hood design practice with the user's rates from the applicable code or the hood maker, e.g. ASHRAE Standard 154)
Questions and answers
3 m hood, 1.2 m deep, 0.3 m³/s per metre or 0.25 m/s?
0.9 m³/s by length, 0.9 m³/s by face: 3,240 m³/h.
Why make-up air?
Without it doors whistle and the hood cannot exhaust its design flow.
Grease filters?
Add their pressure drop to the fan selection.