FireCADCalc

Internal Heat Gains: People, Lighting and Equipment

Sensible and latent heat gains in a room from occupants, lighting and equipment, from the per-person and per-area figures you enter.

Inputs

Examples: Control room 150 m²Panel room, no people

From a handbook for the activity; your figure.

Results

Peak gains; a cooling load method spreads the radiant part over time.

People, sensible0.90000kW
People, latent0.66000kW
Lighting1.5000kW
Equipment2.8125kW
Total sensible5.2125kW
Total5.8725kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Control room 150 m². The inputs, in the units selected above:

InputValue
Number of people12.000 -
Sensible heat per person0.075000 kW
Latent heat per person0.055000 kW
Floor area150.00 m²
Lighting power density0.010000 kW/m²
Lighting use factor100.00 %
Equipment power density0.025000 kW/m²
Equipment diversity factor75.000 %

Applying the formula below gives:

ResultValue
People, sensible0.90000 kW
People, latent0.66000 kW
Lighting1.5000 kW
Equipment2.8125 kW
Total sensible5.2125 kW
Total5.8725 kW

Open this example in the calculator and change any input.

Formula

\(\dot Q_s = n q_{ps} + A q_L F_L + A q_E F_E, \quad \dot Q_l = n q_{pl}\)

Variables

Symbol Meaning SI unit
\(n\) Number of people -
\(q_{ps}\) Sensible heat per person W
\(q_{pl}\) Latent heat per person W
\(A\) Floor area m²
\(q_L\) Lighting power density W/m²
\(F_L\) Lighting use factor -
\(q_E\) Equipment power density W/m²
\(F_E\) Equipment diversity factor -
\(\dot Q_p\) People, sensible W
\(\dot Q_l\) People, latent W
\(\dot Q_L\) Lighting W
\(\dot Q_E\) Equipment W
\(\dot Q_s\) Total sensible W
\(\dot Q_t\) Total W

Method and standards

Sum of gains.

Where it is used

  • Control room, MCC room and office cooling loads.
  • Quick AC sizing.

Common mistakes

  • Nameplate power without diversity.
  • Forgetting latent from people.

Assumptions and limits

  • Peak instantaneous gains.

References

  • Sum of internal gains (ASHRAE Handbook—Fundamentals ch. 18 approach, user figures)

Questions and answers

What do the defaults give?

About 0.9 kW from people (plus 0.66 kW latent), 1.5 kW lighting and 2.8 kW equipment: 5.2 kW sensible.

Control rooms?

Equipment dominates; use the panel makers' heat dissipation.

Why a diversity factor?

Not everything runs at full power at once.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.