Infiltration by the Crack Method (Wind and Stack)

Air infiltration through window and door cracks from crack length, a flow coefficient, wind speed and stack height, with air changes and heat load.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 30 m of crack, 5 m/s wind, 5 °C outsideTall hall, still air, −5 °C, 12 m stack

Results

Wind and stack pressures are added, a conservative simplification. Outside air density from the ideal gas law at standard pressure. Heat load is negative when outside is warmer (sensible gain).

Pressure difference (wind + stack)14.601Pa
Infiltration92.546m³/h
Air changes per hour0.30849
Infiltration heat load492.28W

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 30 m of crack, 5 m/s wind, 5 °C outside. The inputs, in the units selected above:

InputValue
Crack length30.000 m
Flow coefficient at 1 Pa, in L/(s·m) per Paⁿ0.15000 -
Flow exponent0.65000 -
Wind speed5.0000 m/s
Pressure coefficient difference across the building0.80000 -
Height above the neutral plane3.0000 m
Inside temperature20.000 °C
Outside temperature5.0000 °C
Room volume300.00 m³

Applying the formula below gives:

ResultValue
Pressure difference (wind + stack)14.601 Pa
Infiltration92.546 m³/h
Air changes per hour0.30849
Infiltration heat load492.28 W

Open this example in the calculator and change any input.

Formula

\(\Delta p = \Delta C_p\frac{\rho v^2}{2} + \rho gh\frac{|T_i - T_o|}{T_i}, \quad \dot V = CL\Delta p^n\)

Variables

Symbol Meaning SI unit
\(L\) Crack length m
\(C\) Flow coefficient at 1 Pa, in L/(s·m) per Paⁿ -
\(n\) Flow exponent -
\(v\) Wind speed m/s
\(\Delta C_p\) Pressure coefficient difference across the building -
\(h\) Height above the neutral plane m
\(t_i\) Inside temperature K
\(t_o\) Outside temperature K
\(V\) Room volume m³
\(\Delta p\) Pressure difference (wind + stack) Pa
\(\dot V\) Infiltration m³/s
\(ACH\) Air changes per hour -
\(Q\) Infiltration heat load W

Method and standards

Power-law leakage.

Where it is used

  • Heating load estimates.
  • Comparing weather-stripping options.

Common mistakes

  • Adding infiltration and mechanical ventilation without checking pressurisation.
  • Using a leaky crack coefficient for modern windows.

Assumptions and limits

  • Steady wind; uniform cracks.
  • C is in L/(s·m) at 1 Pa in every unit system; convert a US figure (cfm per ft at 0.3 in WC) first.
  • Outside air density at 101 325 Pa with M = 28.9647 kg/kmol; heat load with c_p = 1006 J/(kg·K).

References

  • ASHRAE Handbook—Fundamentals (2017)
  • ch. 16 (power-law leakage Q = C·L·Δp^n; wind and stack pressures)

Questions and answers

Why the exponent 0.65?

Cracks behave between laminar (n = 1) and orifice flow (n = 0.5); 0.65 is the usual average.

When does stack effect dominate?

In tall buildings in cold weather: the pressure grows with height above the neutral plane.

What do the defaults represent?

A room with windows and doors totalling 30 m of crack on a breezy cool day.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.