Worked example
Example: 30 m of crack, 5 m/s wind, 5 °C outside. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Crack length | 30.000 m |
| Flow coefficient at 1 Pa, in L/(s·m) per Paⁿ | 0.15000 - |
| Flow exponent | 0.65000 - |
| Wind speed | 5.0000 m/s |
| Pressure coefficient difference across the building | 0.80000 - |
| Height above the neutral plane | 3.0000 m |
| Inside temperature | 20.000 °C |
| Outside temperature | 5.0000 °C |
| Room volume | 300.00 m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Pressure difference (wind + stack) | 14.601 Pa |
| Infiltration | 92.546 m³/h |
| Air changes per hour | 0.30849 |
| Infiltration heat load | 492.28 W |
Open this example in the calculator and change any input.
Formula
\(\Delta p = \Delta C_p\frac{\rho v^2}{2} + \rho gh\frac{|T_i - T_o|}{T_i}, \quad \dot V = CL\Delta p^n\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(L\) | Crack length | m |
| \(C\) | Flow coefficient at 1 Pa, in L/(s·m) per Paⁿ | - |
| \(n\) | Flow exponent | - |
| \(v\) | Wind speed | m/s |
| \(\Delta C_p\) | Pressure coefficient difference across the building | - |
| \(h\) | Height above the neutral plane | m |
| \(t_i\) | Inside temperature | K |
| \(t_o\) | Outside temperature | K |
| \(V\) | Room volume | m³ |
| \(\Delta p\) | Pressure difference (wind + stack) | Pa |
| \(\dot V\) | Infiltration | m³/s |
| \(ACH\) | Air changes per hour | - |
| \(Q\) | Infiltration heat load | W |
Method and standards
Power-law leakage.
Where it is used
- Heating load estimates.
- Comparing weather-stripping options.
Common mistakes
- Adding infiltration and mechanical ventilation without checking pressurisation.
- Using a leaky crack coefficient for modern windows.
Assumptions and limits
- Steady wind; uniform cracks.
- C is in L/(s·m) at 1 Pa in every unit system; convert a US figure (cfm per ft at 0.3 in WC) first.
- Outside air density at 101 325 Pa with M = 28.9647 kg/kmol; heat load with c_p = 1006 J/(kg·K).
References
- ASHRAE Handbook—Fundamentals (2017)
- ch. 16 (power-law leakage Q = C·L·Δp^n; wind and stack pressures)
Questions and answers
Why the exponent 0.65?
Cracks behave between laminar (n = 1) and orifice flow (n = 0.5); 0.65 is the usual average.
When does stack effect dominate?
In tall buildings in cold weather: the pressure grows with height above the neutral plane.
What do the defaults represent?
A room with windows and doors totalling 30 m of crack on a breezy cool day.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.