FireCADCalc

Solar Heat Gain Through Windows (SHGC Method)

Solar heat gain and conduction heat gain through glazing from its area, solar heat gain coefficient, incident solar irradiance, shading and U-value.

Air conditioning and chillers

Inputs

Examples: 10 m² double glazing, SHGC 0.4, 600 W/m²25 m² solar-control, 750 W/m², 40 % shaded4 m² clear single glass, 400 W/m²

Results

Instantaneous gain; the cooling load it causes lags behind as the room stores heat. Irradiance on the glass depends on orientation, hour and site: take it from a solar data source.

Solar heat gain2,812.5W
Conduction heat gain720.00W
Total heat gain through the glazing3,532.5W

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 10 m² double glazing, SHGC 0.4, 600 W/m². The inputs, in the units selected above:

InputValue
Glazed area10.000 m²
Solar heat gain coefficient of the glazing40.000 %
Solar irradiance on the glass600.00 W/m²
Share not blocked by external shading100.00 %
U-value of the window2.8000 W/(m²·K)
Outdoor temperature35.000 °C
Indoor temperature24.000 °C

Applying the formula below gives:

ResultValue
Solar heat gain2,400.0 W
Conduction heat gain308.00 W
Total heat gain through the glazing2,708.0 W

Open this example in the calculator and change any input.

Formula

\(Q_s = A \cdot SHGC \cdot I \cdot f_s\)

\(Q_c = U A (T_o - T_i), \quad Q = Q_s + Q_c\)

Variables

Symbol Meaning SI unit
\(A\) Glazed area m²
\(SHGC\) Solar heat gain coefficient of the glazing -
\(I\) Solar irradiance on the glass W/m²
\(f_s\) Share not blocked by external shading -
\(U\) U-value of the window W/(m²·K)
\(T_o\) Outdoor temperature K
\(T_i\) Indoor temperature K
\(Q_s\) Solar heat gain W
\(Q_c\) Conduction heat gain W
\(Q\) Total heat gain through the glazing W

Method and standards

The ASHRAE solar heat gain coefficient method: solar gain is the irradiance on the glass times the SHGC and the unshaded share; conduction is U A ΔT.

Where it is used

  • Cooling load estimates for offices, control rooms and labs.
  • Comparing glass types and shading.
  • Explaining hot west-facing rooms.

Common mistakes

  • Using irradiance on a horizontal surface for vertical glass.
  • Using the glass-only SHGC for the whole window.
  • Treating instantaneous gain as the cooling load.

Assumptions and limits

  • Instantaneous gain; storage lag not included.
  • One SHGC on the total irradiance. ASHRAE splits it into the direct beam (with the angle-dependent SHGC) and diffuse (with the hemispherical SHGC); one value is a simplification.

References

  • ASHRAE Handbook—Fundamentals
  • ch. 15 Fenestration (SHGC method)

Questions and answers

How much heat does 10 m² of SHGC 0.4 glass let in at 600 W/m²?

2.4 kW of solar gain plus 0.3 kW by conduction for an 11 K difference: 2.7 kW.

What is SHGC?

The share of incident solar energy that ends up inside, transmitted plus absorbed and re-released: about 0.8 for clear single glass, 0.25 for good solar-control glass.

Where do I get the irradiance?

From solar data for the orientation, month and hour; peak values on east and west glass are often 500–800 W/m².

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.