Worked example
Example: 10 m² double glazing, SHGC 0.4, 600 W/m². The inputs, in the units selected above:
| Input | Value |
|---|---|
| Glazed area | 10.000 m² |
| Solar heat gain coefficient of the glazing | 40.000 % |
| Solar irradiance on the glass | 600.00 W/m² |
| Share not blocked by external shading | 100.00 % |
| U-value of the window | 2.8000 W/(m²·K) |
| Outdoor temperature | 35.000 °C |
| Indoor temperature | 24.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Solar heat gain | 2,400.0 W |
| Conduction heat gain | 308.00 W |
| Total heat gain through the glazing | 2,708.0 W |
Open this example in the calculator and change any input.
Formula
\(Q_s = A \cdot SHGC \cdot I \cdot f_s\)
\(Q_c = U A (T_o - T_i), \quad Q = Q_s + Q_c\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(A\) | Glazed area | m² |
| \(SHGC\) | Solar heat gain coefficient of the glazing | - |
| \(I\) | Solar irradiance on the glass | W/m² |
| \(f_s\) | Share not blocked by external shading | - |
| \(U\) | U-value of the window | W/(m²·K) |
| \(T_o\) | Outdoor temperature | K |
| \(T_i\) | Indoor temperature | K |
| \(Q_s\) | Solar heat gain | W |
| \(Q_c\) | Conduction heat gain | W |
| \(Q\) | Total heat gain through the glazing | W |
Method and standards
The ASHRAE solar heat gain coefficient method: solar gain is the irradiance on the glass times the SHGC and the unshaded share; conduction is U A ΔT.
Where it is used
- Cooling load estimates for offices, control rooms and labs.
- Comparing glass types and shading.
- Explaining hot west-facing rooms.
Common mistakes
- Using irradiance on a horizontal surface for vertical glass.
- Using the glass-only SHGC for the whole window.
- Treating instantaneous gain as the cooling load.
Assumptions and limits
- Instantaneous gain; storage lag not included.
- One SHGC on the total irradiance. ASHRAE splits it into the direct beam (with the angle-dependent SHGC) and diffuse (with the hemispherical SHGC); one value is a simplification.
References
- ASHRAE Handbook—Fundamentals
- ch. 15 Fenestration (SHGC method)
Questions and answers
How much heat does 10 m² of SHGC 0.4 glass let in at 600 W/m²?
2.4 kW of solar gain plus 0.3 kW by conduction for an 11 K difference: 2.7 kW.
What is SHGC?
The share of incident solar energy that ends up inside, transmitted plus absorbed and re-released: about 0.8 for clear single glass, 0.25 for good solar-control glass.
Where do I get the irradiance?
From solar data for the orientation, month and hour; peak values on east and west glass are often 500–800 W/m².