FireCADCalc

Dilution Ventilation for a Solvent or Gas Release

Air flow to dilute an evaporating solvent or released gas to a target concentration, from the release rate, molar mass, mixing factor and conditions.

Inputs

Examples: Toluene 0.5 kg/h to 50 ppmAcetone 1 kg/h to 250 ppm

Your exposure limit or a share of the lower explosive limit.

Results

Dilution suits low-toxicity vapours released slowly and spread out; use local exhaust for toxic or concentrated sources.

Vapour released7.2329L/min
Dilution air needed3,471.8m³/h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Toluene 0.5 kg/h to 50 ppm. The inputs, in the units selected above:

InputValue
Release (evaporation) rate0.50000 kg/h
Molar mass of the substance92.140 kg/kmol
Target concentration (ppm by volume)50.000 -
Mixing (safety) factor3.0000 -
Air temperature25.000 °C
Barometric pressure (absolute)101.33 kPa

Applying the formula below gives:

ResultValue
Vapour released2.2127 L/min
Dilution air needed7,965.7 m³/h

Open this example in the calculator and change any input.

Formula

\(\dot V_g = \frac{\dot m}{M}\cdot\frac{R T}{p}, \quad \dot V = \frac{K \dot V_g}{C \times 10^{-6}}\)

Variables

Symbol Meaning SI unit
\(\dot m\) Release (evaporation) rate kg/s
\(M\) Molar mass of the substance kg/kmol
\(C\) Target concentration (ppm by volume) -
\(K\) Mixing (safety) factor -
\(T\) Air temperature K
\(p\) Barometric pressure (absolute) Pa
\(\dot V_g\) Vapour released m³/s
\(\dot V\) Dilution air needed m³/s

Method and standards

Mass balance.

Where it is used

  • Paint shops, labs, chemical stores.
  • Battery and fuel stores.

Common mistakes

  • Molar volume at the wrong temperature.
  • Using it for toxic point sources.

Assumptions and limits

  • Steady state; perfect mixing allowed for by K.
  • The supply air is taken as free of the substance; a background concentration C_s would raise the flow to K V̇_g/((C − C_s) × 10⁻⁶).

References

  • Dilution ventilation Q = K G / C (ACGIH Industrial Ventilation manual)
  • vapour volume from the ideal gas law

Questions and answers

0.5 kg/h of toluene to 50 ppm with K 3?

About 2.2 m³/s (8,000 m³/h).

What is K?

It allows for poor mixing: 1 for good mixing, up to 10 for poor.

Flammable vapours?

Dilute to a fraction of the LEL as your safety rules require.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.