Air Changes per Hour (ACH) and Ventilation Airflow

Air changes per hour of a room from its size and the supply airflow, and the airflow needed for a target number of air changes.

Fan and blowerAir conditioning and chillersRefrigeration and air-conditioning mechanic examinations

Inputs

Examples: Workshop 20 x 10 x 4 m, 4 000 m³/h, target 6Battery room 6 x 4 x 3 m, 300 m³/h, target 12Boiler house 30 x 20 x 12 m, 60 000 m³/h, target 10

Results

Room volume72.000m³
Air changes per hour4.16671/h
Airflow for the target air changes864.00m³/h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Workshop 20 x 10 x 4 m, 4 000 m³/h, target 6. The inputs, in the units selected above:

InputValue
Room length20.000 m
Room width10.000 m
Room height4.0000 m
Supply (or extract) airflow4,000.0 m³/h
Target air changes per hour6.0000 1/h

Applying the formula below gives:

ResultValue
Room volume800.00 m³
Air changes per hour5.0000 1/h
Airflow for the target air changes4,800.0 m³/h

Open this example in the calculator and change any input.

Formula

\(V = L W H\)

\(n = Q / V\)

\(Q_t = n_t V\)

Variables

Symbol Meaning SI unit
\(L\) length m
\(W\) width m
\(H\) height m
\(Q\) airflow m³/s
\(n_t\) target air changes 1/s
\(V\) room volume m³
\(n\) air changes 1/s
\(Q_t\) airflow for the target m³/s

Method and standards

An air change is a volume of air equal to the room volume; the rate is airflow over volume.

Where it is used

  • Sizing exhaust fans for battery rooms and boiler houses.
  • Checking ventilation in workshops and stores.
  • Converting ventilation rules into fan duty.

Common mistakes

  • Using floor area instead of volume.
  • Assuming perfect mixing in tall spaces.
  • Ignoring makeup air.

Assumptions and limits

  • Perfect mixing; constant room volume.

References

  • ACH = Q / V

Questions and answers

How many air changes does 4 000 m³/h give in a 20 × 10 × 4 m room?

5 per hour; 6 per hour needs 4 800 m³/h.

What air change rate do rooms need?

It depends on use and local codes: battery rooms, boiler houses, kitchens and offices all differ; use the rate your code or standard requires.

Is ACH enough to design ventilation?

Often not: heat removal, fumes or occupancy may need more; check each.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.