Air-Cooled Exchanger: Air-Side Coefficient, Pressure Drop, Fan Power

Air-side film coefficient (Briggs–Young, Ganguli), bundle pressure drop (Robinson–Briggs, Ganguli) and fan and motor power for a finned-tube air cooler.

Thermal power plantRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: Six-row cooler, 11 fins/in, 1.0 in fins on 1.25 in tubes, 3 in pitch, forced draftSmall three-row cooler, 8 fins/in, 2.25 in pitch

Accepted: 10 to 60 mm
Accepted: 2 to 30 mm
Accepted: 0.1 to 3 mm
Accepted: 1.27 to 25.4 1/in
Accepted: 20 to 150 mm
Accepted: 1 to 12
Accepted: 360 to 18,000,000 kg/h
Accepted: 0.1 to 2,000 m²
Accepted: 0.5 to 2 kg/m³
Accepted: 0.01 to 0.05 mPa·s
Accepted: 0.015 to 0.05 W/(m·K)
Accepted: 0.95 to 1.1 kJ/(kg·K)
Accepted: 0 to 100 %
Accepted: 1 to 20
Accepted: 0.5 to 12 m
Accepted: 0.5 to 2 kg/m³
Accepted: 20 to 95 %
Accepted: 50 to 100 %

Results

Ganguli et al.

Fan static pressure taken equal to the air-side loss (induced draft without diffusers); fans should cover at least 40 % of the face area.

Face velocity3.3186m/s
Maximum velocity in the bundle6.3140m/s
Reynolds number (root diameter)12,050
Finned-to-bare area ratio16.540
Briggs–Young coefficient49.510W/(m²·K)
Ganguli (HTRI) coefficient52.682W/(m²·K)
Robinson–Briggs friction factor0.43163
Bundle pressure drop, Robinson–Briggs233.33Pa
Ganguli friction factor0.20904
Bundle pressure drop, Ganguli113.01Pa
Total air-side loss (fan static pressure)129.96Pa
Air flow per fan84.746m³/s
Velocity pressure in the fan ring20.663Pa
Fan brake power, each17.019kW
Motor output power, each17.915kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Six-row cooler, 11 fins/in, 1.0 in fins on 1.25 in tubes, 3 in pitch, forced draft. The inputs, in the units selected above:

InputValue
Fin root diameter (tube OD)31.750 mm
Fin height12.700 mm
Fin thickness0.40000 mm
Fins per unit length11.000 1/in
Tube pitch (equilateral triangular)76.200 mm
Tube rows6.0000 -
Air mass flow1,080,000 kg/h
Bundle face area80.000 m²
Air density at the mean temperature1.1300 kg/m³
Air viscosity0.018800 mPa·s
Air thermal conductivity0.026800 W/(m·K)
Air specific heat1.0070 kJ/(kg·K)
Other air-side losses as a share of the bundle loss15.000 %
Number of fans3.0000 -
Fan diameter4.2700 m
Air density at the fan1.1800 kg/m³
Fan total efficiency75.000 %
Speed reducer efficiency95.000 %

Applying the formula below gives:

ResultValue
Face velocity3.3186 m/s
Maximum velocity in the bundle6.3140 m/s
Reynolds number (root diameter)12,050
Finned-to-bare area ratio16.540
Briggs–Young coefficient49.510 W/(m²·K)
Ganguli (HTRI) coefficient52.682 W/(m²·K)
Robinson–Briggs friction factor0.43163
Bundle pressure drop, Robinson–Briggs233.33 Pa
Ganguli friction factor0.20904
Bundle pressure drop, Ganguli113.01 Pa
Total air-side loss (fan static pressure)129.96 Pa
Air flow per fan84.746 m³/s
Velocity pressure in the fan ring20.663 Pa
Fan brake power, each17.019 kW
Motor output power, each17.915 kW

Open this example in the calculator and change any input.

Formula

\(V_{max} = \frac{P_TV_{face}}{P_T - D_r - 2n_fb\tau}, \quad Nu = 0.38Re^{0.6}Pr^{1/3}\left(\frac{A_{Tot}}{A_o}\right)^{-0.15}, \quad Nu = 0.134Re^{0.681}Pr^{1/3}\left(\frac{s}{b}\right)^{0.2}\left(\frac{s}{\tau}\right)^{0.1134}\)

\(\Delta P = \frac{2fN_rG^2}{\rho}, \quad f_{RB} = 18.93Re^{-0.316}\left(\frac{P_T}{D_r}\right)^{-0.927}, \quad W_{fan} = \frac{(\Delta P_o + \rho V_{fr}^2/2)\dot v_{fan}}{\eta_{fan}}\)

Variables

Symbol Meaning SI unit
\(D_r\) Fin root diameter (tube OD) m
\(b\) Fin height m
\(\tau\) Fin thickness m
\(n_f\) Fins per unit length 1/m
\(P_T\) Tube pitch (equilateral triangular) m
\(N_r\) Tube rows -
\(\dot m_a\) Air mass flow kg/s
\(A_{face}\) Bundle face area m²
\(\rho\) Air density at the mean temperature kg/m³
\(\mu\) Air viscosity Pa·s
\(k\) Air thermal conductivity W/(m·K)
\(c_p\) Air specific heat J/(kg·K)
\(\chi\) Other air-side losses as a share of the bundle loss -
\(n_{fan}\) Number of fans -
\(D_{fan}\) Fan diameter m
\(\rho_{fan}\) Air density at the fan kg/m³
\(\eta_{fan}\) Fan total efficiency -
\(\eta_{sr}\) Speed reducer efficiency -
\(V_{face}\) Face velocity m/s
\(V_{max}\) Maximum velocity in the bundle m/s
\(Re\) Reynolds number (root diameter) -
\(A_{Tot}/A_o\) Finned-to-bare area ratio -
\(h_{BY}\) Briggs–Young coefficient W/(m²·K)
\(h_{G}\) Ganguli (HTRI) coefficient W/(m²·K)
\(f_{RB}\) Robinson–Briggs friction factor -
\(\Delta P_{RB}\) Bundle pressure drop, Robinson–Briggs Pa
\(f_G\) Ganguli friction factor -
\(\Delta P_{G}\) Bundle pressure drop, Ganguli Pa
\(\Delta P_o\) Total air-side loss (fan static pressure) Pa
\(\dot v_{fan}\) Air flow per fan m³/s
\(\rho V_{fr}^2/2\) Velocity pressure in the fan ring Pa
\(W_{fan}\) Fan brake power, each W
\(W_{motor}\) Motor output power, each W

Method and standards

Finned-tube bank correlations for air-side heat transfer and friction, with fan total-pressure power.

Where it is used

  • Sizing process air coolers and air-cooled condensers.
  • Checking fan motor size.

Common mistakes

  • Using standard-air density for the bundle velocity.
  • Forgetting the fan-ring velocity pressure in the fan power.

Assumptions and limits

  • Equilateral triangular pitch, high-fin tubes, three or more rows.

Questions and answers

Why use the face velocity at the mean density?

The mass flow is fixed; the actual velocity through the bundle depends on the air density at the mean air temperature.

What other losses are there?

Louvres, screens, hail guards, fan supports, plenums and walkways: usually 10–25 % of the bundle loss.

What do the defaults represent?

An illustrative case: Six-row cooler, 11 fins/in, 1.0 in fins on 1.25 in tubes, 3 in pitch, forced draft. Replace the inputs with your own data.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Serth, Process Heat Transfer: Principles and Applications (Academic Press, 2007), ch. 12, eqs. 12.1 to 12.18 and Example 12.1 (Briggs and Young 1963; Robinson and Briggs 1966; Ganguli, Tung and Taborek 1985)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.