FireCADCalc

Simplified Delaware Method: Shell-Side Coefficient and Pressure Drop

Shell-side film coefficient from the Simplified Delaware j_H curve and pressure drop from its friction factor fits, for 20 % cut segmental baffles.

Refinery and petrochemicalChemical and fertiliser

Inputs

Examples: Water, 0.5 m shell, 19.05 mm tubes on 23.81 mm triangular, B = 0.2 mOil at low Re, 0.35 m shell, rotated square, B = 0.15 m

Accepted: 36 to 3,600,000 kg/h
Accepted: 100 to 3,000 mm
Accepted: 5 to 60 mm
Accepted: 6 to 100 mm
Accepted: 20 to 3,000 mm
Accepted: 1 to 500
Accepted: 0.001 to 1,000 mPa·s
Accepted: 0.05 to 20
Accepted: 0.5 to 10 kJ/(kg·K)
Accepted: 0.01 to 1 W/(m·K)
Accepted: 0.5 to 2,000 kg/m³

Results

Simplified Delaware method (Wolverine Engineering Data Book curve fits): 20 % cut segmental baffles, TEMA clearances and one pair of sealing strips per ten tube rows, with a built-in safety factor of about 25 % on h_o.

Equivalent diameter13.764mm
Flow area across the bundle0.019992m²
Mass flux1,250.5kg/(m²·s)
Reynolds number (equivalent diameter)24,590
Modified Colburn factor58.290
Shell-side heat transfer coefficient4,517.9W/(m²·K)
Friction factor at B/d_s = 1, ft²/in²0.003071
Friction factor at B/d_s = 0.2, ft²/in²5.6063e-04
Shell-side friction factor0.17111
Shell-side pressure drop (without nozzles)99.988kPa

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Water, 0.5 m shell, 19.05 mm tubes on 23.81 mm triangular, B = 0.2 m. The inputs, in the units selected above:

InputValue
Shell-side mass flow90,000 kg/h
Shell inside diameter500.00 mm
Tube outside diameter19.050 mm
Tube pitch23.810 mm
Tube layoutTriangular
Baffle spacing200.00 mm
Number of baffles20.000 -
Shell-side fluid viscosity0.70000 mPa·s
Viscosity ratio bulk to wall1.2000 -
Specific heat4.1800 kJ/(kg·K)
Thermal conductivity0.62000 W/(m·K)
Density995.00 kg/m³

Applying the formula below gives:

ResultValue
Equivalent diameter13.764 mm
Flow area across the bundle0.019992 m²
Mass flux1,250.5 kg/(m²·s)
Reynolds number (equivalent diameter)24,590
Modified Colburn factor58.290
Shell-side heat transfer coefficient4,517.9 W/(m²·K)
Friction factor at B/d_s = 1, ft²/in²0.003071
Friction factor at B/d_s = 0.2, ft²/in²5.6063e-04
Shell-side friction factor0.17111
Shell-side pressure drop (without nozzles)99.988 kPa

Open this example in the calculator and change any input.

Formula

\(j_H = 0.5\left(1 + \frac{B}{d_s}\right)\left(0.08Re^{0.6821} + 0.7Re^{0.1772}\right), \quad h_o = j_H\frac{k}{D_e}Pr^{1/3}\phi\)

\(\Delta P_f = \frac{fG^2d_s(n_b + 1)}{2\rho D_e\phi}, \quad f = 144\left[f_1 - 1.25\left(1 - \frac{B}{d_s}\right)(f_1 - f_2)\right]\)

Variables

Symbol Meaning SI unit
\(\dot m\) Shell-side mass flow kg/s
\(d_s\) Shell inside diameter m
\(D_o\) Tube outside diameter m
\(P_T\) Tube pitch m
\(\text{layout}\) Tube layout -
\(B\) Baffle spacing m
\(n_b\) Number of baffles -
\(\mu\) Shell-side fluid viscosity Pa·s
\(\mu/\mu_w\) Viscosity ratio bulk to wall -
\(c_p\) Specific heat J/(kg·K)
\(k\) Thermal conductivity W/(m·K)
\(\rho\) Density kg/m³
\(D_e\) Equivalent diameter m
\(a_s\) Flow area across the bundle m²
\(G\) Mass flux kg/(m²·s)
\(Re\) Reynolds number (equivalent diameter) -
\(j_H\) Modified Colburn factor -
\(h_o\) Shell-side heat transfer coefficient W/(m²·K)
\(f_1\) Friction factor at B/d_s = 1, ft²/in² -
\(f_2\) Friction factor at B/d_s = 0.2, ft²/in² -
\(f\) Shell-side friction factor -
\(\Delta P_f\) Shell-side pressure drop (without nozzles) Pa

Method and standards

Simplified Delaware shell-side correlations with Kern's equivalent diameter.

Where it is used

  • First-pass rating and design of shell-and-tube exchangers.
  • Hand checks of simulator results.

Common mistakes

  • Using it for baffle cuts other than 20 %.
  • Forgetting that h_o includes a safety factor.

Assumptions and limits

  • 20 % cut segmental baffles, plain or low-fin tubes; shells 8–42 in.

Questions and answers

How does it differ from the full Delaware method?

It folds the leakage and bypass effects for standard TEMA clearances into one j_H curve with about 25 % margin.1 shows a 22 % lower h_o than the full method.

Why is the baffle cut fixed at 20 %?

The correlation was fitted to that cut; for other cuts use the Bell–Delaware calculator.

What do the defaults represent?

An illustrative case: Water, 0.5 m shell, 19.05 mm tubes on 23.81 mm triangular, B = 0.2 m. Replace the inputs with your own data.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Serth, Process Heat Transfer: Principles and Applications (Academic Press, 2007), sec. 3.8 (eqs. 3.20, 3.21, Fig. 3.12), sec. 5.3.2 (eqs. 5.6 to 5.11), Appendix 5.A and Example 5.1

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.