Worked example
Example: Six-row cooler, 11 fins/in, 1.0 in fins on 1.25 in tubes, 3 in pitch, forced draft. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Fin root diameter (tube OD) | 31.750 mm |
| Fin height | 12.700 mm |
| Fin thickness | 0.40000 mm |
| Fins per unit length | 11.000 1/in |
| Tube pitch (equilateral triangular) | 76.200 mm |
| Tube rows | 6.0000 - |
| Air mass flow | 1,080,000 kg/h |
| Bundle face area | 80.000 m² |
| Air density at the mean temperature | 1.1300 kg/m³ |
| Air viscosity | 0.018800 mPa·s |
| Air thermal conductivity | 0.026800 W/(m·K) |
| Air specific heat | 1.0070 kJ/(kg·K) |
| Other air-side losses as a share of the bundle loss | 15.000 % |
| Number of fans | 3.0000 - |
| Fan diameter | 4.2700 m |
| Air density at the fan | 1.1800 kg/m³ |
| Fan total efficiency | 75.000 % |
| Speed reducer efficiency | 95.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Face velocity | 3.3186 m/s |
| Maximum velocity in the bundle | 6.3140 m/s |
| Reynolds number (root diameter) | 12,050 |
| Finned-to-bare area ratio | 16.540 |
| Briggs–Young coefficient | 49.510 W/(m²·K) |
| Ganguli (HTRI) coefficient | 52.682 W/(m²·K) |
| Robinson–Briggs friction factor | 0.43163 |
| Bundle pressure drop, Robinson–Briggs | 233.33 Pa |
| Ganguli friction factor | 0.20904 |
| Bundle pressure drop, Ganguli | 113.01 Pa |
| Total air-side loss (fan static pressure) | 129.96 Pa |
| Air flow per fan | 84.746 m³/s |
| Velocity pressure in the fan ring | 20.663 Pa |
| Fan brake power, each | 17.019 kW |
| Motor output power, each | 17.915 kW |
Open this example in the calculator and change any input.
Formula
\(V_{max} = \frac{P_TV_{face}}{P_T - D_r - 2n_fb\tau}, \quad Nu = 0.38Re^{0.6}Pr^{1/3}\left(\frac{A_{Tot}}{A_o}\right)^{-0.15}, \quad Nu = 0.134Re^{0.681}Pr^{1/3}\left(\frac{s}{b}\right)^{0.2}\left(\frac{s}{\tau}\right)^{0.1134}\)
\(\Delta P = \frac{2fN_rG^2}{\rho}, \quad f_{RB} = 18.93Re^{-0.316}\left(\frac{P_T}{D_r}\right)^{-0.927}, \quad W_{fan} = \frac{(\Delta P_o + \rho V_{fr}^2/2)\dot v_{fan}}{\eta_{fan}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(D_r\) | Fin root diameter (tube OD) | m |
| \(b\) | Fin height | m |
| \(\tau\) | Fin thickness | m |
| \(n_f\) | Fins per unit length | 1/m |
| \(P_T\) | Tube pitch (equilateral triangular) | m |
| \(N_r\) | Tube rows | - |
| \(\dot m_a\) | Air mass flow | kg/s |
| \(A_{face}\) | Bundle face area | m² |
| \(\rho\) | Air density at the mean temperature | kg/m³ |
| \(\mu\) | Air viscosity | Pa·s |
| \(k\) | Air thermal conductivity | W/(m·K) |
| \(c_p\) | Air specific heat | J/(kg·K) |
| \(\chi\) | Other air-side losses as a share of the bundle loss | - |
| \(n_{fan}\) | Number of fans | - |
| \(D_{fan}\) | Fan diameter | m |
| \(\rho_{fan}\) | Air density at the fan | kg/m³ |
| \(\eta_{fan}\) | Fan total efficiency | - |
| \(\eta_{sr}\) | Speed reducer efficiency | - |
| \(V_{face}\) | Face velocity | m/s |
| \(V_{max}\) | Maximum velocity in the bundle | m/s |
| \(Re\) | Reynolds number (root diameter) | - |
| \(A_{Tot}/A_o\) | Finned-to-bare area ratio | - |
| \(h_{BY}\) | Briggs–Young coefficient | W/(m²·K) |
| \(h_{G}\) | Ganguli (HTRI) coefficient | W/(m²·K) |
| \(f_{RB}\) | Robinson–Briggs friction factor | - |
| \(\Delta P_{RB}\) | Bundle pressure drop, Robinson–Briggs | Pa |
| \(f_G\) | Ganguli friction factor | - |
| \(\Delta P_{G}\) | Bundle pressure drop, Ganguli | Pa |
| \(\Delta P_o\) | Total air-side loss (fan static pressure) | Pa |
| \(\dot v_{fan}\) | Air flow per fan | m³/s |
| \(\rho V_{fr}^2/2\) | Velocity pressure in the fan ring | Pa |
| \(W_{fan}\) | Fan brake power, each | W |
| \(W_{motor}\) | Motor output power, each | W |
Method and standards
Finned-tube bank correlations for air-side heat transfer and friction, with fan total-pressure power.
Where it is used
- Sizing process air coolers and air-cooled condensers.
- Checking fan motor size.
Common mistakes
- Using standard-air density for the bundle velocity.
- Forgetting the fan-ring velocity pressure in the fan power.
Assumptions and limits
- Equilateral triangular pitch, high-fin tubes, three or more rows.
Questions and answers
Why use the face velocity at the mean density?
The mass flow is fixed; the actual velocity through the bundle depends on the air density at the mean air temperature.
What other losses are there?
Louvres, screens, hail guards, fan supports, plenums and walkways: usually 10–25 % of the bundle loss.
What do the defaults represent?
An illustrative case: Six-row cooler, 11 fins/in, 1.0 in fins on 1.25 in tubes, 3 in pitch, forced draft. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Serth, Process Heat Transfer: Principles and Applications (Academic Press, 2007), ch. 12, eqs. 12.1 to 12.18 and Example 12.1 (Briggs and Young 1963; Robinson and Briggs 1966; Ganguli, Tung and Taborek 1985)