Worked example
Example: Steam condensing at 1 atm, x = 0.5, 20 mm tube, 100 kg/(m2 s). The inputs, in the units selected above:
| Input | Value |
|---|---|
| Total mass flux | 100.00 kg/(m²·s) |
| Tube inside diameter | 20.000 mm |
| Vapour quality | 50.000 % |
| Saturation minus wall temperature | 10.000 K |
| Pressure | 101.33 kPa |
| Critical pressure | 22,064 kPa |
| Liquid density | 958.40 kg/m³ |
| Vapour density | 0.59800 kg/m³ |
| Liquid viscosity (at saturation for Shah) | 0.28200 mPa·s |
| Vapour viscosity | 0.012300 mPa·s |
| Liquid thermal conductivity | 0.67900 W/(m·K) |
| Liquid specific heat | 4.2160 kJ/(kg·K) |
| Latent heat | 2,257.0 kJ/kg |
Applying the formula below gives:
| Result | Value |
|---|---|
| Reynolds number, total flow as liquid | 7,092.2 |
| Liquid Prandtl number | 1.7510 |
| All-liquid coefficient (Dittus–Boelter) | 1,176.3 W/(m²·K) |
| Dimensionless vapour velocity (regime map) | 4.7174 |
| Lockhart–Martinelli parameter | 0.034167 |
| Shah coefficient | 20,532 W/(m²·K) |
| Boyko–Kruzhilin coefficient | 33,308 W/(m²·K) |
| Two-phase multiplier (Müller-Steinhagen–Heck) | 655.20 |
| Breber et al. coefficient, exponent 0.45 | 21,771 W/(m²·K) |
| Void fraction (Chisholm slip) | 99.607 % |
| Stratified-flow coefficient | 13,301 W/(m²·K) |
Open this example in the calculator and change any input.
Formula
\(h_{Shah} = h_{LO}\left[(1 - x)^{0.8} + \frac{3.8x^{0.76}(1 - x)^{0.04}}{P_r^{0.38}}\right], \quad h_{BK} = h_{LO}\left[1 + x\frac{\rho_L - \rho_V}{\rho_V}\right]^{1/2}\)
\(h_{Breber} = h_{LO}(\phi_{LO}^2)^{0.45}, \quad h_{strat} = 0.728\varepsilon_V^{0.75}\left[\frac{k_L^3\rho_L(\rho_L - \rho_V)g\lambda}{\mu_L(T_{sat} - T_w)D_i}\right]^{1/4}, \quad j^* = \frac{xG}{[D_ig\rho_V(\rho_L - \rho_V)]^{1/2}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(G\) | Total mass flux | kg/(m²·s) |
| \(D_i\) | Tube inside diameter | m |
| \(x\) | Vapour quality | - |
| \(T_{sat} - T_w\) | Saturation minus wall temperature | K |
| \(P\) | Pressure | Pa |
| \(P_c\) | Critical pressure | Pa |
| \(\rho_L\) | Liquid density | kg/m³ |
| \(\rho_V\) | Vapour density | kg/m³ |
| \(\mu_L\) | Liquid viscosity (at saturation for Shah) | Pa·s |
| \(\mu_V\) | Vapour viscosity | Pa·s |
| \(k_L\) | Liquid thermal conductivity | W/(m·K) |
| \(c_{p,L}\) | Liquid specific heat | J/(kg·K) |
| \(\lambda\) | Latent heat | J/kg |
| \(Re_{LO}\) | Reynolds number, total flow as liquid | - |
| \(Pr_L\) | Liquid Prandtl number | - |
| \(h_{LO}\) | All-liquid coefficient (Dittus–Boelter) | W/(m²·K) |
| \(j^*\) | Dimensionless vapour velocity (regime map) | - |
| \(X_{tt}\) | Lockhart–Martinelli parameter | - |
| \(h_{Shah}\) | Shah coefficient | W/(m²·K) |
| \(h_{BK}\) | Boyko–Kruzhilin coefficient | W/(m²·K) |
| \(\phi_{LO}^2\) | Two-phase multiplier (Müller-Steinhagen–Heck) | - |
| \(h_{Breber}\) | Breber et al. coefficient, exponent 0.45 | W/(m²·K) |
| \(\varepsilon_V\) | Void fraction (Chisholm slip) | - |
| \(h_{strat}\) | Stratified-flow coefficient | W/(m²·K) |
Method and standards
Two-phase multiplier and Nusselt-type correlations for condensation inside tubes.
Where it is used
- Air-cooled condensers and tube-side process condensers.
- Zone-by-zone condenser rating.
Common mistakes
- Applying an annular-flow correlation to stratified flow.
- Using wall-temperature properties in Shah's correlation.
Assumptions and limits
- Local coefficient at one quality; integrate over the condensing range for the mean.
Questions and answers
Which result should I use?
Check the regime: annular flow (high j*, low X_tt) → Shah, Breber or Boyko–Kruzhilin; stratified flow → the Nusselt-type stratified value; in between, interpolate with Breber's rules.
Why does Shah fail near x = 1?
His multiplier contains (1 − x) terms and goes to zero for pure vapour; it is meant for qualities up to about 0.999 with a liquid film present.
What do the defaults represent?
An illustrative case: Steam condensing at 1 atm, x = 0.5, 20 mm tube, 100 kg/(m2 s). Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Serth, Process Heat Transfer: Principles and Applications (Academic Press, 2007), sec. 11.6, eqs. 11.50 to 11.57 and Examples 11.4 and 11.5 (Shah 1979; Boyko and Kruzhilin 1967; Breber, Palen and Taborek 1980)