FireCADCalc

Shell-side Coefficient and Pressure Drop by Kern's Method

Shell-side equivalent diameter, cross-flow area, Reynolds number, film coefficient and pressure drop of a baffled shell-and-tube exchanger by Kern's method.

Process steam and utilitiesRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: Triangular 25 mm tubes on 31.25 mm, 0.6 m shell, kerosene 20 kg/sViscous oil 8 kg/s, 0.5 m shell, square 1 in on 1.25 in

Accepted: 0.1 to 3 m
Accepted: 5 to 100 mm
Accepted: 6 to 150 mm
Accepted: 0.02 to 3 m
Accepted: 0.5 to 20 m
Accepted: 36 to 3,600,000 kg/h
Accepted: 1 to 2,000 kg/m³
Accepted: 0.001 to 1,000 mPa·s
Accepted: 0.001 to 1,000 mPa·s
Accepted: 0.01 to 2 W/(m·K)
Accepted: 0.5 to 6 kJ/(kg·K)

Results

Kern's correlation h_oD_e/k = 0.36 Re^0.55 Pr^1/3 (μ_b/μ_w)^0.14 for 2,000 < Re < 10⁶ with 25 % baffle cut; it ignores leakage and bypass streams, so the Bell–Delaware method is preferred for final design.

Shell-side equivalent diameter18.073mm
Clearance between tubes6.2500mm
Cross-flow area0.036000m²
Shell-side mass velocity555.56kg/(m²·s)
Shell-side Reynolds number25,101
Shell-side film coefficient1,280.3W/(m²·K)
Friction factor0.25955
Number of baffles15.000
Shell-side pressure drop28.520kPa

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Triangular 25 mm tubes on 31.25 mm, 0.6 m shell, kerosene 20 kg/s. The inputs, in the units selected above:

InputValue
Shell inside diameter0.60000 m
Tube outside diameter25.000 mm
Tube pitch31.250 mm
Tube layoutTriangular
Baffle spacing0.30000 m
Tube length4.8800 m
Shell-side flow72,000 kg/h
Shell fluid density780.00 kg/m³
Viscosity at the bulk temperature0.40000 mPa·s
Viscosity at the wall temperature0.55000 mPa·s
Shell fluid conductivity0.13000 W/(m·K)
Shell fluid specific heat2.4700 kJ/(kg·K)

Applying the formula below gives:

ResultValue
Shell-side equivalent diameter18.073 mm
Clearance between tubes6.2500 mm
Cross-flow area0.036000 m²
Shell-side mass velocity555.56 kg/(m²·s)
Shell-side Reynolds number25,101
Shell-side film coefficient1,280.3 W/(m²·K)
Friction factor0.25955
Number of baffles15.000
Shell-side pressure drop28.520 kPa

Open this example in the calculator and change any input.

Formula

\(D_e = \frac{4(P_T^2 - \pi d_o^2/4)}{\pi d_o}\ \text{(square)}, \quad A_s = \frac{D_sCB}{P_T}, \quad Re_s = \frac{G_sD_e}{\mu_b}\)

\(\frac{h_oD_e}{k} = 0.36Re_s^{0.55}Pr^{1/3}\left(\frac{\mu_b}{\mu_w}\right)^{0.14}, \quad \Delta p_s = \frac{fG_s^2(N_b + 1)D_s}{2\rho D_e\phi_s}, \quad f = e^{0.576 - 0.19\ln Re_s}\)

Variables

Symbol Meaning SI unit
\(D_s\) Shell inside diameter m
\(d_o\) Tube outside diameter m
\(P_T\) Tube pitch m
\(\text{layout}\) Tube layout -
\(B\) Baffle spacing m
\(L\) Tube length m
\(\dot m_s\) Shell-side flow kg/s
\(\rho\) Shell fluid density kg/m³
\(\mu_b\) Viscosity at the bulk temperature Pa·s
\(\mu_w\) Viscosity at the wall temperature Pa·s
\(k\) Shell fluid conductivity W/(m·K)
\(c_p\) Shell fluid specific heat J/(kg·K)
\(D_e\) Shell-side equivalent diameter m
\(C\) Clearance between tubes m
\(A_s\) Cross-flow area m²
\(G_s\) Shell-side mass velocity kg/(m²·s)
\(Re_s\) Shell-side Reynolds number -
\(h_o\) Shell-side film coefficient W/(m²·K)
\(f\) Friction factor -
\(N_b\) Number of baffles -
\(\Delta p_s\) Shell-side pressure drop Pa

Method and standards

Where it is used

  • Preliminary shell-and-tube design.
  • Quick checks of vendor data sheets.

Common mistakes

  • Using the shell diameter as the hydraulic diameter.
  • Forgetting the viscosity correction in the pressure drop.

Assumptions and limits

  • Segmental baffles with about 25 % cut; no leakage or bypass correction.

Questions and answers

How accurate is Kern's method?

It is a simple and conservative estimate; it can overpredict the coefficient where leakage and bypass are large and is used mainly for preliminary design and checks.

What does the baffle spacing change?

Closer baffles raise the shell-side velocity: the coefficient rises with Re0.55 but the pressure drop roughly with Re1.8 and the number of baffles.

What do the defaults represent?

An illustrative case: Triangular 25 mm tubes on 31.25 mm, 0.6 m shell, kerosene 20 kg/s. Replace the inputs with your own data.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Kakaç, Liu and Pramuanjaroenkij, Heat Exchangers: Selection, Rating and Thermal Design, 3rd ed. (CRC Press, 2012), sec. 9.4.1 (Kern method), Example 9.2

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.