Double-Pipe (Hairpin) Exchanger: Coefficients, Area, Hairpins and Δp

Inner-tube and annulus film coefficients, fouled and clean overall coefficients, area, number of hairpins and pressure drops of a double-pipe heat exchanger.

Process steam and utilitiesRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: Oil cooler: 1.25 in in 2 in pipe, 6 m legs, oil in annulus, water insideGas oil heater 150 kW, dTm 60 K, 2 in in 3 in, 4.5 m

Accepted: 0.01 to 100,000 kW
Accepted: 0.5 to 500 K
Accepted: 5 to 300 mm
Accepted: 6 to 350 mm
Accepted: 10 to 500 mm
Accepted: 0.5 to 20 m
Accepted: 1 to 400 W/(m·K)
Accepted: 0 to 0.01 m²·K/W
Accepted: 0 to 0.01 m²·K/W
Accepted: 0.36 to 360,000 kg/h
Accepted: 1 to 2,000 kg/m³
Accepted: 0.001 to 1,000 mPa·s
Accepted: 0.01 to 2 W/(m·K)
Accepted: 0.5 to 1,000
Accepted: 0.36 to 360,000 kg/h
Accepted: 1 to 2,000 kg/m³
Accepted: 0.001 to 1,000 mPa·s
Accepted: 0.01 to 2 W/(m·K)
Accepted: 0.5 to 1,000

Results

Turbulent Prandtl-type correlation Nu = (f/2)RePr/[1 + 8.7(f/2)^½(Pr − 1)] with f = (1.58 ln Re − 3.28)⁻², used by for both streams; the annulus uses D_h = D_i − d_o for Re and friction and D_e = (D_i² − d_o²)/d_o for heat transfer. Return bends, inlet and outlet losses are extra.

One stream has Re below 10,000; the turbulent correlation becomes uncertain.

Inner tube velocity1.5580m/s
Inner Reynolds number68,015
Inner film coefficient5,482.7W/(m²·K)
Annulus velocity3.0357m/s
Annulus Reynolds number (on D_h)8,963.3
Annulus film coefficient (on D_e)362.67W/(m²·K)
Fouled overall coefficient (outside area)275.74W/(m²·K)
Clean overall coefficient326.48W/(m²·K)
Required outside area5.4399m²
Hairpins required (exact)3.4194
Hairpins installed (rounded up)4.0000
Inner tube pressure drop (straight lengths)32.297kPa
Annulus pressure drop (straight lengths)599.57kPa

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Oil cooler: 1.25 in in 2 in pipe, 6 m legs, oil in annulus, water inside. The inputs, in the units selected above:

InputValue
Heat duty60.000 kW
Mean temperature difference40.000 K
Inner tube inside diameter35.100 mm
Inner tube outside diameter42.200 mm
Outer pipe inside diameter52.500 mm
Hairpin leg length6.0000 m
Inner tube wall conductivity45.000 W/(m·K)
Fouling resistance, inside1.7600e-04 m²·K/W
Fouling resistance, annulus side3.5200e-04 m²·K/W
Inner tube flow5,400.0 kg/h
Inner fluid density995.00 kg/m³
Inner fluid viscosity0.80000 mPa·s
Inner fluid conductivity0.62000 W/(m·K)
Inner fluid Prandtl number5.4000 -
Annulus flow7,200.0 kg/h
Annulus fluid density860.00 kg/m³
Annulus fluid viscosity3.0000 mPa·s
Annulus fluid conductivity0.13000 W/(m·K)
Annulus fluid Prandtl number45.000 -

Applying the formula below gives:

ResultValue
Inner tube velocity1.5580 m/s
Inner Reynolds number68,015
Inner film coefficient5,482.7 W/(m²·K)
Annulus velocity3.0357 m/s
Annulus Reynolds number (on D_h)8,963.3
Annulus film coefficient (on D_e)362.67 W/(m²·K)
Fouled overall coefficient (outside area)275.74 W/(m²·K)
Clean overall coefficient326.48 W/(m²·K)
Required outside area5.4399 m²
Hairpins required (exact)3.4194
Hairpins installed (rounded up)4.0000
Inner tube pressure drop (straight lengths)32.297 kPa
Annulus pressure drop (straight lengths)599.57 kPa

Open this example in the calculator and change any input.

Formula

\(Nu = \frac{(f/2)RePr}{1 + 8.7(f/2)^{1/2}(Pr - 1)}, \quad f = (1.58\ln Re - 3.28)^{-2}\)

\(\frac{1}{U_f} = \frac{d_o}{d_ih_i} + \frac{d_oR_{fi}}{d_i} + \frac{d_o\ln(d_o/d_i)}{2k_w} + R_{fo} + \frac{1}{h_o}, \quad \Delta p = 4f\frac{2LN_{hp}}{D}\frac{\rho u^2}{2}\)

Variables

Symbol Meaning SI unit
\(Q\) Heat duty W
\(\Delta T_m\) Mean temperature difference K
\(d_i\) Inner tube inside diameter m
\(d_o\) Inner tube outside diameter m
\(D_i\) Outer pipe inside diameter m
\(L\) Hairpin leg length m
\(k_w\) Inner tube wall conductivity W/(m·K)
\(R_{fi}\) Fouling resistance, inside m²·K/W
\(R_{fo}\) Fouling resistance, annulus side m²·K/W
\(\dot m_i\) Inner tube flow kg/s
\(\rho_i\) Inner fluid density kg/m³
\(\mu_i\) Inner fluid viscosity Pa·s
\(k_i\) Inner fluid conductivity W/(m·K)
\(Pr_i\) Inner fluid Prandtl number -
\(\dot m_a\) Annulus flow kg/s
\(\rho_a\) Annulus fluid density kg/m³
\(\mu_a\) Annulus fluid viscosity Pa·s
\(k_a\) Annulus fluid conductivity W/(m·K)
\(Pr_a\) Annulus fluid Prandtl number -
\(u_i\) Inner tube velocity m/s
\(Re_i\) Inner Reynolds number -
\(h_i\) Inner film coefficient W/(m²·K)
\(u_a\) Annulus velocity m/s
\(Re_a\) Annulus Reynolds number (on D_h) -
\(h_o\) Annulus film coefficient (on D_e) W/(m²·K)
\(U_f\) Fouled overall coefficient (outside area) W/(m²·K)
\(U_c\) Clean overall coefficient W/(m²·K)
\(A_o\) Required outside area m²
\(A_o/A_{hp}\) Hairpins required (exact) -
\(N_{hp}\) Hairpins installed (rounded up) -
\(\Delta p_i\) Inner tube pressure drop (straight lengths) Pa
\(\Delta p_a\) Annulus pressure drop (straight lengths) Pa

Method and standards

Double-pipe exchanger thermal design.

Where it is used

  • Small process heaters and coolers.
  • Sizing hairpins for high-pressure duties.

Common mistakes

  • Using D_h for the annulus heat-transfer coefficient.
  • Forgetting the return-bend losses.

Assumptions and limits

  • Turbulent flow, counterflow, constant properties.

Questions and answers

Why two different diameters for the annulus?

Friction acts on both walls, so the hydraulic diameter D_i − d_o sets Re and Δp; heat passes only through the inner tube, so the heat-transfer diameter is (D_i² − d_o²)/d_o.

When are hairpins chosen?

For small duties (below about 50 m²), high pressures or temperature crosses, since true counterflow is possible.

What do the defaults represent?

An illustrative case: Oil cooler: 1.25 in in 2 in pipe, 6 m legs, oil in annulus, water inside. Replace the inputs with your own data.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Kakaç, Liu and Pramuanjaroenkij, Heat Exchangers: Selection, Rating and Thermal Design, 3rd ed. (CRC Press, 2012), sec. 7.3, eqs. 7.1 to 7.7 and Example 7.1

Related calculators