Condenser Bundle Coefficient: Vertical In-Tube or Horizontal (Kern)

Film condensing coefficient for a vertical in-tube condenser (laminar, wavy or turbulent film) or a horizontal shell-side bundle by Kern's loading method.

Distillery and ethanolRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: Steam at 0.5 bar condensing in 40 vertical tubes (turbulent film)

Accepted: 0.36 to 1,800,000 kg/h
Accepted: 1 to 50,000
Accepted: 0.2 to 30 m
Accepted: 3 to 100 mm
Accepted: 4 to 120 mm
Accepted: 50 to 2,000 kg/m³
Accepted: 0 to 500 kg/m³
Accepted: 0.01 to 100 mPa·s
Accepted: 0.01 to 1 W/(m·K)
Accepted: 0.5 to 10 kJ/(kg·K)
Accepted: 10 to 3,000 kJ/kg

Results

Nusselt (Re ≤ 30), Kutateladze-type wavy (30–1600) and Labuntsov-type turbulent (> 1600) correlations for the whole film, as given by after Butterworth.

Properties at the film temperature T_f = 0.75 T_w + 0.25 T_sat; repeat with properties at the new T_w until it settles. Interfacial shear and vapour superheat are not included.

Condensate loading1.0851kg/m
Film Reynolds number 4Γ/μ_L13,564
Film regime (1 laminar, 2 wavy, 3 turbulent; 0 horizontal bundle)3.0000
Condensing coefficient8,142.6W/(m²·K)
Condensing surface16.588m²
Film temperature drop51.197K
Condensate Prandtl number2.0060
Jakob number c_pΔT/λ0.093288
Subcooling correction (Sadasivan–Lienhard)1.0130
Coefficient with subcooling correction8,248.6W/(m²·K)

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Steam at 0.5 bar condensing in 40 vertical tubes (turbulent film). The inputs, in the units selected above:

InputValue
Condensate flow10,800 kg/h
Condenser typeVertical, condensing inside the tubes
Number of tubes40.000 -
Tube length6.0000 m
Tube inside diameter22.000 mm
Tube outside diameter25.000 mm
Condensate density965.00 kg/m³
Vapour density0.31000 kg/m³
Condensate viscosity0.32000 mPa·s
Condensate thermal conductivity0.67000 W/(m·K)
Condensate specific heat4.2000 kJ/(kg·K)
Latent heat2,305.0 kJ/kg

Applying the formula below gives:

ResultValue
Condensate loading1.0851 kg/m
Film Reynolds number 4Γ/μ_L13,564
Film regime (1 laminar, 2 wavy, 3 turbulent; 0 horizontal bundle)3.0000
Condensing coefficient8,142.6 W/(m²·K)
Condensing surface16.588 m²
Film temperature drop51.197 K
Condensate Prandtl number2.0060
Jakob number c_pΔT/λ0.093288
Subcooling correction (Sadasivan–Lienhard)1.0130
Coefficient with subcooling correction8,248.6 W/(m²·K)

Open this example in the calculator and change any input.

Formula

\(\text{vertical: } \Gamma = \frac{W}{n_t\pi D_i}, \; Re = \frac{4\Gamma}{\mu_L}, \; h = \frac{Re\,K}{1.08Re^{1.22} - 5.2}\;(30 < Re \le 1600), \quad K = \left[\frac{k_L^3\rho_L(\rho_L - \rho_V)g}{\mu_L^2}\right]^{1/3}\)

\(\text{horizontal: } h = 1.52\left[\frac{k_L^3\rho_L(\rho_L - \rho_V)g}{4\mu_L\Gamma^*}\right]^{1/3}, \quad \Gamma^* = \frac{W}{Ln_t^{2/3}}, \quad \frac{h}{h_{Nu}} = \left[1 + \left(0.683 - \frac{0.228}{Pr_L}\right)\zeta\right]^{1/4}\)

Variables

Symbol Meaning SI unit
\(W\) Condensate flow kg/s
\(\text{bundle}\) Condenser type -
\(n_t\) Number of tubes -
\(L\) Tube length m
\(D_i\) Tube inside diameter m
\(D_o\) Tube outside diameter m
\(\rho_L\) Condensate density kg/m³
\(\rho_V\) Vapour density kg/m³
\(\mu_L\) Condensate viscosity Pa·s
\(k_L\) Condensate thermal conductivity W/(m·K)
\(c_{p,L}\) Condensate specific heat J/(kg·K)
\(\lambda\) Latent heat J/kg
\(\Gamma\) Condensate loading kg/m
\(Re_f\) Film Reynolds number 4Γ/μ_L -
\(\text{regime}\) Film regime (1 laminar, 2 wavy, 3 turbulent; 0 horizontal bundle) -
\(h\) Condensing coefficient W/(m²·K)
\(A\) Condensing surface m²
\(T_{sat} - T_w\) Film temperature drop K
\(Pr_L\) Condensate Prandtl number -
\(\zeta\) Jakob number c_pΔT/λ -
\(h/h_{Nu}\) Subcooling correction (Sadasivan–Lienhard) -
\(h_c\) Coefficient with subcooling correction W/(m²·K)

Method and standards

Nusselt film condensation with wavy and turbulent film corrections and Kern's bundle drainage allowance.

Where it is used

  • Sizing overhead condensers and vapour condensers.
  • Choosing between vertical and horizontal condenser layouts.

Common mistakes

  • Using the vapour flow per tube for a horizontal bundle without Kern's n_t^(2/3).
  • Ignoring the change of viscosity with the wall temperature.

Assumptions and limits

  • Pure saturated vapours, gravity-controlled films.

Questions and answers

Why does the horizontal bundle give a higher coefficient?

Each tube carries a short film; even with Kern's n_t^(2/3) drainage allowance the film stays thinner than on a long vertical tube.

Is the vapour density needed?

Only at higher pressures; at about 1 atm it is negligible next to the liquid density, as Designers assume.

What do the defaults represent?

An illustrative case: Steam at 0.5 bar condensing in 40 vertical tubes (turbulent film). Replace the inputs with your own data.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Serth, Process Heat Transfer: Principles and Applications (Academic Press, 2007), secs. 11.3 to 11.5, eqs. 11.26, 11.35, 11.36, 11.39, 11.40, 11.47 and Examples 11.1 and 11.2

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.