Worked example
Example: 400 kg magnetite, 5 % HCl. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Deposit (as Fe₃O₄) | 400.00 kg |
| Excess acid | 50.000 % |
| HCl strength of the cleaning solution | 5.0000 % |
| Solution density | 1,025.0 kg/m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| HCl (100 %) needed | 755.83 kg |
| Cleaning solution | 15.117 t |
| Solution volume | 14.748 m³ |
Open this example in the calculator and change any input.
Formula
\(m_{HCl} = m_d \frac{8 M_{HCl}}{M_{Fe_3O_4}}(1 + k_x), \quad m_s = \frac{m_{HCl}}{w}, \quad V_s = \frac{m_s}{\rho}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(m_d\) | Deposit (as Fe₃O₄) | kg |
| \(k_x\) | Excess acid | - |
| \(w\) | HCl strength of the cleaning solution | - |
| \(\rho\) | Solution density | kg/m³ |
| \(m_{HCl}\) | HCl (100 %) needed | kg |
| \(m_s\) | Cleaning solution | kg |
| \(V_s\) | Solution volume | m³ |
Method and standards
Stoichiometry of magnetite dissolution in hydrochloric acid, Fe₃O₄ + 8 HCl → FeCl₂ + 2 FeCl₃ + 4 H₂O, with IUPAC atomic masses; the acid is raised by the excess entered and diluted to the solution strength.
Where it is used
- Pre-commissioning and operational cleaning.
Common mistakes
- Deposit as iron instead of Fe₃O₄.
Assumptions and limits
- Magnetite only. The ferric chloride formed attacks the base metal and consumes more acid (often controlled with a reducing agent); copper and other deposits also take acid. The excess is the only allowance for all of these.
References
- Fe₃O₄ + 8 HCl → FeCl₂ + 2 FeCl₃ + 4 H₂O with IUPAC atomic masses
Questions and answers
How is the deposit mass found?
From deposit weight density (g/m²) on cut tube samples times the waterside area.
Why excess acid?
Acid is consumed by other deposits and must stay above a minimum strength to the end.
Inhibitor?
Always inhibited acid, to protect the base metal.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.