Condensing Economiser Heat Recovery

Sensible and latent heat recovered by cooling flue gas below its water dew point, with the condensate formed and the efficiency gain, from the fuel analysis.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationPulp and paperFood, dairy and textileIAPWS-IF97 (water and steam)BoilerEconomiser and air preheaterStack and chimney

Inputs

Examples: Natural gas boiler 0.5 t/h, gas 150 to 45 °CNatural gas, 160 to 70 °C (above the dew point)Bagasse 25 t/h, 170 to 55 °C

Ultimate analysis, as fired, by mass

Set by the coldest water available (return water or make-up).

Results

Condensate from flue gas is acidic: the condensing section needs stainless steel or another corrosion-resistant material and a neutralised drain.

Total heat recovered786.07kW
Sensible heat343.32kW
Latent heat from condensation442.74kW
Water condensed665.78kg/h
Efficiency gain on GCV (points)10.198%
Water dew point of the flue gas58.388°C

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Natural gas boiler 0.5 t/h, gas 150 to 45 °C. The inputs, in the units selected above:

InputValue
Carbon74.868 %
Hydrogen25.132 %
Oxygen0 %
Nitrogen0 %
Sulphur0 %
Ash0 %
Moisture0 %
Excess air15.000 %
Air humidity (kg water per kg dry air)0.013000 kg/kg
Fuel firing rate500.00 kg/h
Flue gas temperature entering150.00 °C
Flue gas temperature leaving45.000 °C
Flue gas pressure (absolute)1.0132 bar
Gross calorific value of the fuel, as fired55,500 kJ/kg

Applying the formula below gives:

ResultValue
Total heat recovered786.07 kW
Sensible heat343.32 kW
Latent heat from condensation442.74 kW
Water condensed665.78 kg/h
Efficiency gain on GCV (points)10.198 %
Water dew point of the flue gas58.388 °C

Open this example in the calculator and change any input.

Formula

\(\dot Q_s = \dot m_f\left[m_{dg}\,\Delta h_{dg} + m_{w}\,\Delta h_v\right] \qquad n_c = \max\!\left(0,\; n_w - n_{dg}\,\frac{p_{sat}(T_2)}{p - p_{sat}(T_2)}\right)\)

\(\dot m_c = \dot m_f\,n_c\,M_{H_2O} \qquad \dot Q_l = \dot m_c\,h_{fg}(T_2) \qquad \dot Q = \dot Q_s + \dot Q_l \qquad \Delta\eta = \frac{\dot Q}{\dot m_f\,GCV}\)

\(T_{dp} = T_{sat}\!\left(\frac{n_w}{n_w + n_{dg}}\,p\right)\)

Variables

Symbol Meaning SI unit
\(C\), \(H\), \(O\), \(N\), \(S\), \(A\), \(M\) ultimate analysis as fired, mass fractions –
\(EA\) excess air –
\(\omega\) air humidity, kg water per kg dry air kg/kg
\(\dot m_f\) fuel firing rate kg/s
\(T_1\) flue gas temperature entering K
\(T_2\) flue gas temperature leaving K
\(p\) flue gas pressure, absolute Pa
\(GCV\) gross calorific value J/kg
\(\dot Q\) total heat recovered W
\(\dot Q_s\) sensible heat recovered W
\(\dot Q_l\) latent heat from condensation W
\(\dot m_c\) water condensed kg/s
\(\Delta\eta\) efficiency gain on GCV –
\(T_{dp}\) water dew point of the flue gas K
\(m_{dg}\), \(m_w\) dry flue gas and water vapour per kg of fuel kg/kg
\(\Delta h_{dg}\), \(\Delta h_v\) enthalpy drop of dry gas and vapour from \(T_1\) to \(T_2\) J/kg
\(n_w\), \(n_{dg}\) water vapour and dry gas per kg of fuel kmol/kg
\(n_c\) water condensed per kg of fuel kmol/kg
\(p_{sat}\), \(T_{sat}\) saturation pressure and temperature of water (IF97) Pa, K
\(h_{fg}\) latent heat at \(T_2\) (IF97) J/kg
\(M_{H_2O}\) molar mass of water, 18.015 kg/kmol kg/kmol

Method and standards

Flue gas from FireCAD's combustion balance; sensible heat from NIST Shomate enthalpies of the dry gas and of all the water as vapour; condensate from Dalton's law with the gas leaving saturated at T₂; latent heat and saturation from IAPWS-IF97. The latent heat is taken at the outlet temperature, a small simplification against the gradual condensation between the dew point and T₂.

Where it is used

  • Gas-fired process and heating boilers with a cold water sink (make-up, process water, district heating return).
  • Food, dairy, textile and laundry plants with large hot water demands.
  • Comparing a standard economiser with a condensing one.

Common mistakes

  • Expecting latent recovery without water cold enough to reach the dew point.
  • Using carbon steel in the condensing section: the condensate is acidic.
  • Forgetting the condensate drain and its neutralisation.
  • Quoting efficiency above 100 % on NCV and comparing it with GCV figures.

Assumptions and limits

  • Gas leaves saturated at T₂ when below its dew point; no acid condensation counted.
  • Water is all vapour at T₁; latent heat at T₂. Sensible heat uses ideal-gas Shomate enthalpies and the latent heat IF97; the two bases differ negligibly at near-atmospheric partial pressure.
  • Equilibrium at T₂ gives the most condensate; a real economiser whose water inlet is above T₂ over part of the surface condenses less.
  • For a gaseous fuel enter its analysis by mass in the ultimate-analysis boxes (natural gas, mostly methane: about 75 % C and 25 % H).
  • A warning appears when the GCV differs from the Channiwala–Parikh estimate by more than 15 %.

References

  • IAPWS R7-97(2012) IF97 (saturation)
  • NIST Chemistry WebBook Shomate equations
  • Dalton's law of partial pressures

Questions and answers

How much heat does a condensing economiser recover?

A natural gas boiler burning 0.5 t/h of gas at 15 % excess air, cooling the flue gas from 150 to 45 °C, recovers 343 kW of sensible heat and 443 kW of latent heat, condensing 666 kg/h of water: 10.2 points of efficiency on GCV.

Why is the latent part so large for natural gas?

Methane is a quarter hydrogen by mass, so its flue gas carries much water vapour, dew point about 58 °C. Coal and oil have less hydrogen, a lower dew point and much less to recover.

What water can cool the gas that low?

Cold make-up water, low-temperature process water or return water below about 40–50 °C. Without a cold sink the gas cannot reach its dew point and only sensible heat is recovered.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.