FireCADCalc

Flue Gas Velocity Through a Tube Bank

Free flow area across a row of tubes and the flue gas velocity through it from gas flow, temperature, pressure and molar mass (ideal gas), against an erosion limit.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolBoilerEconomiser and air preheater

Inputs

Examples: Convection bankEconomiser

Results

Free flow area14.760m²
Gas density0.44335kg/m³
Gas velocity6.7918m/s
Share of the limit56.598%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Convection bank. The inputs, in the units selected above:

InputValue
Flue gas flow160.00 t/h
Gas temperature in the bank500.00 °C
Flue gas molar mass28.500 kg/kmol
Gas pressure (absolute)100.00 kPa
Duct width across the tubes6.0000 m
Tube length exposed (duct depth)5.0000 m
Tubes in one row60.000 -
Tube outside diameter50.800 mm
Velocity limit for the fuel's ash12.000 m/s

Applying the formula below gives:

ResultValue
Free flow area14.760 m²
Gas density0.44335 kg/m³
Gas velocity6.7918 m/s
Share of the limit56.598 %

Open this example in the calculator and change any input.

Formula

\(A_f = L (W - n d_o), \quad \rho_g = \frac{p M_g}{1000\,R\,T_g}, \quad v = \frac{\dot m_g}{\rho_g A_f}\)

Variables

Symbol Meaning SI unit
\(\dot m_g\) Flue gas flow kg/s
\(T_g\) Gas temperature in the bank K
\(M_g\) Flue gas molar mass kg/kmol
\(p\) Gas pressure (absolute) Pa
\(W\) Duct width across the tubes m
\(L\) Tube length exposed (duct depth) m
\(n\) Tubes in one row -
\(d_o\) Tube outside diameter m
\(v_{lim}\) Velocity limit for the fuel's ash m/s
\(A_f\) Free flow area m²
\(\rho_g\) Gas density kg/m³
\(v\) Gas velocity m/s
\(R\) universal gas constant, 8.314 J/(mol·K) (the 1000 converts \(M_g\) from kg/kmol) J/(mol·K)
\(v/v_{lim}\) Share of the limit -

Method and standards

Continuity through the free area between the tubes of one row, with the ideal-gas density at the bank temperature and pressure.

Where it is used

  • Convection bank and economiser design.
  • Erosion failure analysis.

Common mistakes

  • Duct area used without tubes.

Assumptions and limits

  • Uniform flow.
  • In-line banks: the gap between tubes of one row sets the area. In staggered banks the diagonal gap can be smaller and then sets the peak velocity; it is not computed here.

References

  • Free area A = L (W − n d); ideal gas density; velocity limit by fuel ash (user input)

Questions and answers

Why does erosion rise so fast with velocity?

Erosion rate rises roughly with the cube of velocity or more.

What limit?

Low for high-ash or sandy fuels (bagasse, husk); higher for oil and gas: use your design practice.

Staggered banks?

Check the diagonal gap too; the minimum gap sets the peak velocity.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.