Worked example
Example: Natural gas boiler 0.5 t/h, gas 150 to 45 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Carbon | 74.868 % |
| Hydrogen | 25.132 % |
| Oxygen | 0 % |
| Nitrogen | 0 % |
| Sulphur | 0 % |
| Ash | 0 % |
| Moisture | 0 % |
| Excess air | 15.000 % |
| Air humidity (kg water per kg dry air) | 0.013000 kg/kg |
| Fuel firing rate | 500.00 kg/h |
| Flue gas temperature entering | 150.00 °C |
| Flue gas temperature leaving | 45.000 °C |
| Flue gas pressure (absolute) | 1.0132 bar |
| Gross calorific value of the fuel, as fired | 55,500 kJ/kg |
Applying the formula below gives:
| Result | Value |
|---|---|
| Total heat recovered | 786.07 kW |
| Sensible heat | 343.32 kW |
| Latent heat from condensation | 442.74 kW |
| Water condensed | 665.78 kg/h |
| Efficiency gain on GCV (points) | 10.198 % |
| Water dew point of the flue gas | 58.388 °C |
Open this example in the calculator and change any input.
Formula
\(\dot Q_s = \dot m_f\left[m_{dg}\,\Delta h_{dg} + m_{w}\,\Delta h_v\right] \qquad n_c = \max\!\left(0,\; n_w - n_{dg}\,\frac{p_{sat}(T_2)}{p - p_{sat}(T_2)}\right)\)
\(\dot m_c = \dot m_f\,n_c\,M_{H_2O} \qquad \dot Q_l = \dot m_c\,h_{fg}(T_2) \qquad \dot Q = \dot Q_s + \dot Q_l \qquad \Delta\eta = \frac{\dot Q}{\dot m_f\,GCV}\)
\(T_{dp} = T_{sat}\!\left(\frac{n_w}{n_w + n_{dg}}\,p\right)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(C\), \(H\), \(O\), \(N\), \(S\), \(A\), \(M\) | ultimate analysis as fired, mass fractions | – |
| \(EA\) | excess air | – |
| \(\omega\) | air humidity, kg water per kg dry air | kg/kg |
| \(\dot m_f\) | fuel firing rate | kg/s |
| \(T_1\) | flue gas temperature entering | K |
| \(T_2\) | flue gas temperature leaving | K |
| \(p\) | flue gas pressure, absolute | Pa |
| \(GCV\) | gross calorific value | J/kg |
| \(\dot Q\) | total heat recovered | W |
| \(\dot Q_s\) | sensible heat recovered | W |
| \(\dot Q_l\) | latent heat from condensation | W |
| \(\dot m_c\) | water condensed | kg/s |
| \(\Delta\eta\) | efficiency gain on GCV | – |
| \(T_{dp}\) | water dew point of the flue gas | K |
| \(m_{dg}\), \(m_w\) | dry flue gas and water vapour per kg of fuel | kg/kg |
| \(\Delta h_{dg}\), \(\Delta h_v\) | enthalpy drop of dry gas and vapour from \(T_1\) to \(T_2\) | J/kg |
| \(n_w\), \(n_{dg}\) | water vapour and dry gas per kg of fuel | kmol/kg |
| \(n_c\) | water condensed per kg of fuel | kmol/kg |
| \(p_{sat}\), \(T_{sat}\) | saturation pressure and temperature of water (IF97) | Pa, K |
| \(h_{fg}\) | latent heat at \(T_2\) (IF97) | J/kg |
| \(M_{H_2O}\) | molar mass of water, 18.015 kg/kmol | kg/kmol |
Method and standards
Flue gas from FireCAD's combustion balance; sensible heat from NIST Shomate enthalpies of the dry gas and of all the water as vapour; condensate from Dalton's law with the gas leaving saturated at T₂; latent heat and saturation from IAPWS-IF97. The latent heat is taken at the outlet temperature, a small simplification against the gradual condensation between the dew point and T₂.
Where it is used
- Gas-fired process and heating boilers with a cold water sink (make-up, process water, district heating return).
- Food, dairy, textile and laundry plants with large hot water demands.
- Comparing a standard economiser with a condensing one.
Common mistakes
- Expecting latent recovery without water cold enough to reach the dew point.
- Using carbon steel in the condensing section: the condensate is acidic.
- Forgetting the condensate drain and its neutralisation.
- Quoting efficiency above 100 % on NCV and comparing it with GCV figures.
Assumptions and limits
- Gas leaves saturated at T₂ when below its dew point; no acid condensation counted.
- Water is all vapour at T₁; latent heat at T₂. Sensible heat uses ideal-gas Shomate enthalpies and the latent heat IF97; the two bases differ negligibly at near-atmospheric partial pressure.
- Equilibrium at T₂ gives the most condensate; a real economiser whose water inlet is above T₂ over part of the surface condenses less.
- For a gaseous fuel enter its analysis by mass in the ultimate-analysis boxes (natural gas, mostly methane: about 75 % C and 25 % H).
- A warning appears when the GCV differs from the Channiwala–Parikh estimate by more than 15 %.
References
- IAPWS R7-97(2012) IF97 (saturation)
- NIST Chemistry WebBook Shomate equations
- Dalton's law of partial pressures
Questions and answers
How much heat does a condensing economiser recover?
A natural gas boiler burning 0.5 t/h of gas at 15 % excess air, cooling the flue gas from 150 to 45 °C, recovers 343 kW of sensible heat and 443 kW of latent heat, condensing 666 kg/h of water: 10.2 points of efficiency on GCV.
Why is the latent part so large for natural gas?
Methane is a quarter hydrogen by mass, so its flue gas carries much water vapour, dew point about 58 °C. Coal and oil have less hydrogen, a lower dew point and much less to recover.
What water can cool the gas that low?
Cold make-up water, low-temperature process water or return water below about 40–50 °C. Without a cold sink the gas cannot reach its dew point and only sensible heat is recovered.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.