Slip Coupling or Eddy-current Drive: Slip Loss and Efficiency

Slip power lost in a magnetic or eddy-current coupling driving a pump, from motor and load speeds and load torque, and the worst-case loss for a fan-law load.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: 1,780 rpm motor, pump at 1,200 rpm, 600 N.mNear full speed 1,780 to 1,740 rpm, 800 N.mFan at half speed, 1,480 to 740 rpm, 200 N.m

Accepted: 9.5493 to 9,549.3 rpm
Accepted: 0.95493 to 9,549.3 rpm
Accepted: 0.01 to 1,000,000 N·m
Accepted: 0.001 to 100,000 kW

Results

Torque is the same on both sides of a slip coupling, so efficiency equals the speed ratio and the lost power appears as heat in the conductor or oil. On a friction-only (cubic) pump system the slip loss peaks at 2/3 speed at 4/27, about 15 % of full-load power; a static head lowers that peak.

Input power30.997kW
Load power15.499kW
Slip loss15.499kW
Coupling efficiency50.000%
Slip50.000%
Peak slip loss on a cubic load (at 2/3 speed)13.333kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 1,780 rpm motor, pump at 1,200 rpm, 600 N.m. The inputs, in the units selected above:

InputValue
Motor speed1,780.0 rpm
Load speed1,200.0 rpm
Load torque at this speed600.00 N·m
Load power at full speed (for the peak loss)150.00 kW

Applying the formula below gives:

ResultValue
Input power111.84 kW
Load power75.398 kW
Slip loss36.442 kW
Coupling efficiency67.416 %
Slip32.584 %
Peak slip loss on a cubic load (at 2/3 speed)22.222 kW

Open this example in the calculator and change any input.

Formula

\(P_{slip} = T(n_m - n_l), \quad \eta = \frac{n_l}{n_m}, \quad P_{slip,max} = \frac{4}{27}P_r\ \ (\text{cubic load})\)

Variables

Symbol Meaning SI unit
\(n_m\) Motor speed rad/s
\(n_l\) Load speed rad/s
\(T\) Load torque at this speed N·m
\(P_r\) Load power at full speed (for the peak loss) W
\(P_{in}\) Input power W
\(P_{out}\) Load power W
\(P_{slip}\) Slip loss W
\(\eta\) Coupling efficiency -
\(s\) Slip -
\(P_{slip,max}\) Peak slip loss on a cubic load (at 2/3 speed) W

Method and standards

Slip power of torque-transmitting couplings.

Where it is used

  • Comparing slip couplings with VFDs.
  • Sizing coupling cooling.

Common mistakes

  • Assuming slip couplings save energy like a VFD at low speed.
  • Using rated torque at reduced speed.

Assumptions and limits

  • Windage and friction neglected.

Questions and answers

Why is efficiency the speed ratio?

Input power is T × motor speed and output T × load speed; with equal torque their ratio is n_l/n_m.

Where is the worst loss?

For a centrifugal load with torque ∝ speed², the slip power (n_m − n_l)·k n_l² peaks at n_l = 2n_m/3, where it is 4/27 of full-load power.

What do the defaults represent?

A 1,780 rpm motor driving a pump at 1,200 rpm with 600 N·m: 111.8 kW in, 75.4 kW out, 36.4 kW of slip heat and 67 % efficiency; a 150 kW friction-only system peaks at 22 kW of slip loss.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Karassik, Messina, Cooper and Heald, Pump Handbook, 4th ed. (McGraw-Hill, 2008), sec. 9.2.1, permanent magnet adjustable speed drives and eddy-current couplings (slip power equations, Fig. 7)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.