Worked example
Example: Illustrative 15-storey building. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Height of the highest outlet above the pump | 45.000 m |
| Pressure needed at the highest outlet (gauge) | 1.5000 bar |
| Friction loss in risers and fittings | 6.0000 m |
| Pressure available at the pump suction (gauge) | 0.20000 bar |
| Design flow | 15.000 m³/h |
| Pump-set efficiency | 60.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Pump discharge pressure (gauge) | 6.4914 bar |
| Pressure the pump must add | 6.2914 bar |
| Pump head | 64.283 m |
| Pump input power | 4.3690 kW |
| Pressure at the lowest outlet (at pump level) | 6.4914 bar |
Open this example in the calculator and change any input.
Formula
\(p_d = p_r + \rho g (h + h_f), \quad \Delta p = p_d - p_s, \quad P = \frac{\dot V\Delta p}{\eta}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(h\) | Height of the highest outlet above the pump | m |
| \(p_r\) | Pressure needed at the highest outlet (gauge) | Pa |
| \(h_f\) | Friction loss in risers and fittings | m |
| \(p_s\) | Pressure available at the pump suction (gauge) | Pa |
| \(\dot V\) | Design flow | m³/s |
| \(\eta\) | Pump-set efficiency | - |
| \(p_d\) | Pump discharge pressure (gauge) | Pa |
| \(\Delta p\) | Pressure the pump must add | Pa |
| \(H\) | Pump head | m |
| \(P\) | Pump input power | W |
| \(p_{low}\) | Pressure at the lowest outlet (at pump level) | Pa |
Method and standards
Booster pump.
Where it is used
- High-rise water supply and pressure zones.
- Commercial and industrial buildings.
Common mistakes
- Sizing for the sum of all fixtures.
- Forgetting pressure at the lowest floors.
Assumptions and limits
- Water at about 20 °C; design flow as entered.
References
- Hydrostatic pressure balance of a building riser
Questions and answers
What pressure does a booster need for a 15-storey building?
About 6.5 bar for 45 m of height, 6 m of friction and 1.5 bar at the top.
Why add pressure-reducing valves?
Lower floors would see the full pump pressure, wasting water and damaging fittings.
What do the defaults represent?
An illustrative building with the top outlet 45 m above the pump, 1.5 bar wanted there, 6 m of friction and 0.2 bar at the suction.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.