Impeller Trimming: Diameter for a New Duty Point

Impeller diameter that moves a centrifugal pump onto a lower duty point, by the affinity laws along the system parabola, with the power saving.

Inputs

Examples: Illustrative 260 mm pump trimmed for 85 m3/h at 40 mSmall cutLarge high-head pump

Accepted: 20 to 3,000 mm
Accepted: 0.1 to 3,000 m
Accepted: 0.0036 to 180,000 m³/h
Accepted: 0.1 to 3,000 m
Accepted: 0.0036 to 180,000 m³/h
Accepted: 0.1 to 3,000 m

Results

The full-diameter curve is taken as H = H₀ − aQ² through the shut-off head and the known point. By the affinity laws a smaller impeller moves each point along a parabola through the origin (Q ∝ D, H ∝ D²), so the full-diameter point on the parabola through the duty point fixes the trim ratio D₂/D₁ = Q_d/Q*. The affinity laws overestimate the trim a little for large cuts: trim in steps, more than about 20 % is rarely advisable, and efficiency falls slightly.

Trimmed impeller diameter230.36mm
Trim ratio88.600%
Full-diameter point on the same system parabola95.937m³/h
Head at that point50.955m
Power at the trimmed duty as a share of the full-impeller power on the same parabola69.551%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 260 mm pump trimmed for 85 m3/h at 40 m. The inputs, in the units selected above:

InputValue
Full impeller diameter260.00 mm
Shut-off head of the full impeller62.000 m
Flow at a known point on the full-diameter curve100.00 m³/h
Head at that point50.000 m
Duty flow wanted85.000 m³/h
Duty head wanted40.000 m

Applying the formula below gives:

ResultValue
Trimmed impeller diameter230.36 mm
Trim ratio88.600 %
Full-diameter point on the same system parabola95.937 m³/h
Head at that point50.955 m
Power at the trimmed duty as a share of the full-impeller power on the same parabola69.551 %

Open this example in the calculator and change any input.

Formula

\(H = H_0 - aQ^2, \quad a = \frac{H_0 - H_1}{Q_1^2}, \quad Q^* = \sqrt{\frac{H_0}{a + H_d/Q_d^2}}, \quad \frac{D_2}{D_1} = \frac{Q_d}{Q^*}\)

Variables

Symbol Meaning SI unit
\(D_1\) Full impeller diameter m
\(H_0\) Shut-off head of the full impeller m
\(Q_1\) Flow at a known point on the full-diameter curve m³/s
\(H_1\) Head at that point m
\(Q_d\) Duty flow wanted m³/s
\(H_d\) Duty head wanted m
\(D_2\) Trimmed impeller diameter m
\(D_2/D_1\) Trim ratio -
\(Q^*\) Full-diameter point on the same system parabola m³/s
\(H^*\) Head at that point m
\((D_2/D_1)^3\) Power at the trimmed duty as a share of the full-impeller power on the same parabola -

Method and standards

Impeller trim.

Where it is used

  • Matching an oversized pump to its real duty instead of throttling.
  • Energy audits of pumping systems.

Common mistakes

  • Scaling the diameter with the duty flow alone (Q_d/Q₁), ignoring the parabola.
  • Trimming below the maker's minimum diameter.

Assumptions and limits

  • Parabolic pump curve; affinity laws; efficiency held.

References

  • Affinity laws for impeller diameter along the system parabola

Questions and answers

How do I calculate the trimmed impeller diameter?

Find where the parabola H = (H_d/Q_d²)Q² meets the full-diameter curve; the trim ratio is Q_d divided by the flow at that point.

How much can an impeller be trimmed?

Typically down to the smallest diameter on the maker's curve, often about 80 % of the full size.

What do the defaults represent?

A pump with a 260 mm impeller giving 50 m at 100 m³/h (62 m shut-off) to be trimmed for 85 m³/h at 40 m.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Karassik, Messina, Cooper and Heald, Pump Handbook, 4th ed. (McGraw-Hill, 2008)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.