Worked example
Example: 30 kW input at 35 m. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Measured electrical input | 30.000 kW |
| Measured differential head | 35.000 m |
| Pump efficiency (from the curve at the estimated duty) | 72.000 % |
| Motor efficiency at this load | 93.000 % |
| Liquid density | 998.00 kg/m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Shaft power | 27.900 kW |
| Estimated flow | 211.12 m³/h |
Open this example in the calculator and change any input.
Formula
\(Q = \frac{P_e\, \eta_m\, \eta_p}{\rho g H}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P_e\) | Measured electrical input | W |
| \(H\) | Measured differential head | m |
| \(\eta_p\) | Pump efficiency (from the curve at the estimated duty) | - |
| \(\eta_m\) | Motor efficiency at this load | - |
| \(\rho\) | Liquid density | kg/m³ |
| \(P_s\) | Shaft power | W |
| \(Q\) | Estimated flow | m³/s |
Method and standards
Energy balance reversed.
Where it is used
- Pump surveys without meters.
- Troubleshooting.
Common mistakes
- Using nameplate efficiency at part load.
- Head from suction gauge only.
Assumptions and limits
- Efficiencies known.
References
- Q = P_e η_m η_p / (ρ g H)
Questions and answers
30 kW input at 35 m head?
About 211 m³/h with 72 % and 93 % efficiencies.
How accurate?
Only as good as the efficiencies: the flow is proportional to η_p η_m, so a 5-point error in pump efficiency at 72 % changes the flow by about 7 %.
Better method?
A clamp-on ultrasonic flowmeter.