Worked example
Example: 50 m shut-off, 40 m at 100 m³/h; 15 m static, 30 m at 100 m³/h. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Pump shut-off head | 50.000 m |
| A pump flow on its curve | 100.00 m³/h |
| Pump head at that flow | 40.000 m |
| Static head of the system | 15.000 m |
| A system flow | 100.00 m³/h |
| System head at that flow (static + friction) | 30.000 m |
| Pump efficiency at the duty | 75.000 % |
| Liquid density | 998.00 kg/m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Flow at the operating point | 118.32 m³/h |
| Head at the operating point | 36.000 m |
| Shaft power at the operating point | 15.440 kW |
Open this example in the calculator and change any input.
Formula
\(H_{pump} = H_0 - aQ^2, \quad H_{sys} = H_s + bQ^2, \quad Q^* = \sqrt{\frac{H_0 - H_s}{a + b}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(H_0\) | Pump shut-off head | m |
| \(Q_r\) | A pump flow on its curve | m³/s |
| \(H_r\) | Pump head at that flow | m |
| \(H_s\) | Static head of the system | m |
| \(Q_s\) | A system flow | m³/s |
| \(H_{s,Q}\) | System head at that flow (static + friction) | m |
| \(\eta\) | Pump efficiency at the duty | - |
| \(\rho\) | Liquid density | kg/m³ |
| \(Q\) | Flow at the operating point | m³/s |
| \(H\) | Head at the operating point | m |
| \(P\) | Shaft power at the operating point | W |
Method and standards
Intersection of two parabolas.
Where it is used
- Pump selection and troubleshooting.
- Energy studies.
Common mistakes
- Ignoring static head.
- Extrapolating the pump curve.
Assumptions and limits
- Parabolic curve shapes.
- The pump efficiency is a fixed input, not read at the computed operating point: take it from the maker's curve at the flow found and repeat if it differs.
References
- Parabolic pump and system curves (Textbook fluid mechanics (White, Fluid Mechanics); Hydraulic Institute)
Questions and answers
50 m shut-off, 40 m at 100 m³/h; system 15 m static, 30 m at 100 m³/h?
Operating point about 118 m³/h at 36.0 m.
Why not exactly the design point?
Pumps run where the curves cross, not where the datasheet says.
How to move the point?
Throttle (raise the system curve), trim the impeller or change speed.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.