FireCADCalc

Choked (Critical) Gas Flow Through an Orifice or Leak

Mass flow of a gas through an orifice, nozzle or leak when choked (sonic), from the upstream pressure and temperature, area, discharge coefficient and γ.

Process steam and utilitiesRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: Air leak, 3 mm at 7 bar(a), 20 °CSteam 6 bar(a), 160 °C, 5 mm nozzle Cd 0.95Nitrogen 2 bar(a) to 1.5 bar(a) (not choked)

Results

Ideal gas with constant γ: for steam near saturation, or gases at high pressure, the real-gas flow differs by a few per cent.

Critical pressure ratio0.54573
Mass flow (choked, or subsonic when not choked)60.129kg/h
Free air or gas at 0 °C, 101.325 kPa74.812Nm³/h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Air leak, 3 mm at 7 bar(a), 20 °C. The inputs, in the units selected above:

InputValue
Upstream pressure (absolute)7.0000 bar
Upstream temperature20.000 °C
Orifice diameter3.0000 mm
Discharge coefficient0.62000 -
Ratio of specific heats1.4000 -
Molar mass28.960 kg/kmol
Downstream pressure (absolute)1.0132 bar

Applying the formula below gives:

ResultValue
Critical pressure ratio0.52828
Mass flow (choked, or subsonic when not choked)26.066 kg/h
Free air or gas at 0 °C, 101.325 kPa20.174 Nm³/h

Open this example in the calculator and change any input.

Formula

\(\dot m = C_d A p_0 \sqrt{\frac{2\gamma}{(\gamma - 1) R T_0}\left[\left(\frac{p_b}{p_0}\right)^{2/\gamma} - \left(\frac{p_b}{p_0}\right)^{(\gamma + 1)/\gamma}\right]}\ \ \left(\frac{p_b}{p_0} > \frac{p^*}{p_0}\right)\) \(\dot m = C_d A p_0 \sqrt{\frac{\gamma}{R T_0}} \left(\frac{2}{\gamma + 1}\right)^{\frac{\gamma + 1}{2(\gamma - 1)}}, \quad \frac{p^*}{p_0} = \left(\frac{2}{\gamma + 1}\right)^{\frac{\gamma}{\gamma - 1}}\)

Variables

Symbol Meaning SI unit
\(p_0\) Upstream pressure (absolute) Pa
\(T_0\) Upstream temperature K
\(d\) Orifice diameter m
\(C_d\) Discharge coefficient -
\(\gamma\) Ratio of specific heats -
\(M\) Molar mass kg/kmol
\(p_b\) Downstream pressure (absolute) Pa
\(p^*/p_0\) Critical pressure ratio -
\(\dot m\) Mass flow (choked) kg/s
\(Q_N\) Free air or gas at 0 °C, 101.325 kPa Nm³/s

Method and standards

Sonic flow at the throat.

Where it is used

  • Compressed air leak surveys.
  • Relief and vent estimates.

Common mistakes

  • Gauge pressure for p₀.
  • Applying it when not choked.

Assumptions and limits

  • Ideal gas, isentropic to the throat, constant γ; steam near saturation and high-pressure gases deviate by a few per cent.
  • When not choked the subsonic isentropic nozzle flow is shown.

References

  • Isentropic nozzle at sonic throat: ṁ = C_d A p₀ √(γ/(R T₀)) (2/(γ+1))^((γ+1)/(2(γ−1)))

Questions and answers

Air leak through a 3 mm hole at 7 bar(a) and 20 °C?

About 7.2 g/s, 20 Nm³/h, with C_d 0.62.

When is flow choked?

When the downstream pressure is below about 0.53 of upstream (air): then flow depends only on upstream conditions.

Why use it for leaks?

Plant air at 7 bar leaking to atmosphere is always choked.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators