Underfloor Heating: Floor Surface and Water Temperatures

Floor surface temperature for a heat output by the EN 1264 basic curve, with mean and flow water temperatures, loop flow and output at a 29 °C floor.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 60 W/m² in a 20 °C room, R 0.10Bathroom 90 W/m² at 24 °C, tiles R 0.06

EN 1264: 29 °C for occupied zones; higher for bathrooms and perimeter zones.

Results

One-dimensional estimate: the pipe spacing and the downward loss are not modelled; use the system maker's tables for final design.

Mean floor surface temperature25.656°C
Mean water temperature31.656°C
Flow (supply) temperature34.156°C
Loop water flow206.40kg/h
Output at the floor temperature limit0.10001kW/m²

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 60 W/m² in a 20 °C room, R 0.10. The inputs, in the units selected above:

InputValue
Required heat output0.060000 kW/m²
Room temperature20.000 °C
Thermal resistance above the pipes (screed and covering)0.10000 m²·K/W
Water temperature drop5.0000 K
Floor area of the loop20.000 m²
Floor surface temperature limit29.000 °C

Applying the formula below gives:

ResultValue
Mean floor surface temperature25.656 °C
Mean water temperature31.656 °C
Flow (supply) temperature34.156 °C
Loop water flow206.40 kg/h
Output at the floor temperature limit0.10001 kW/m²

Open this example in the calculator and change any input.

Formula

\(q = 8.92(\theta_F - \theta_i)^{1.1}, \quad \theta_w = \theta_F + qR, \quad \dot m = \frac{qA}{c_p\Delta\theta_w}\)

Variables

Symbol Meaning SI unit
\(q\) Required heat output W/m²
\(\theta_i\) Room temperature K
\(R\) Thermal resistance above the pipes (screed and covering) m²·K/W
\(\Delta\theta_w\) Water temperature drop K
\(A\) Floor area of the loop m²
\(\theta_F\) Mean floor surface temperature K
\(\theta_w\) Mean water temperature K
\(\theta_V\) Flow (supply) temperature K
\(\dot m\) Loop water flow kg/s
\(\theta_{F,max}\) Floor surface temperature limit K
\(q_{max}\) Output at the floor temperature limit W/m²

Method and standards

EN 1264 basic curve.

Where it is used

  • Heat pump floor heating.
  • Checking floor coverings.

Common mistakes

  • Ignoring floor surface limits.
  • Thick rugs on heated floors.

Assumptions and limits

  • The water temperature is a one-dimensional estimate, θ_w = θ_F + qR: EN 1264's full method also uses the pipe spacing, pipe size and the logarithmic water-to-room temperature difference, so the water temperature can be underestimated, more so for wide pipe spacing.

  • The floor temperature limit defaults to 29 °C (occupied zones); EN 1264 allows higher surface temperatures in bathrooms and perimeter zones: enter the limit that applies.

  • One-dimensional; uniform floor.

References

  • EN 1264-2 basic characteristic curve q = 8.92(θ_F,m − θ_i)^1.1 W/m²; one-dimensional conduction through the floor layers

Questions and answers

How much can a floor give?

At a 29 °C surface in a 20 °C room, about 100 W/m²; more needs perimeter zones at up to 35 °C.

Why do carpets matter?

They add resistance above the pipes, so the water must be hotter for the same output.

What do the defaults represent?

A living room needing 60 W/m² through screed and a thin floor covering.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.