FireCADCalc

Supply Air Flow and Supply State from Room Loads

Supply air mass and volume flow for a room from its sensible and latent loads, room condition and supply temperature, with the supply humidity and SHR.

Inputs

Examples: Room 24 °C 50 %, 35 + 8 kW, supply 13 °CDry room, sensible onlyHigh latent at 95 kPa, supply 14 °C

Results

Dry-air mass flow17,557kg/h
Supply air volume (at the supply state)15,486m³/h
Supply humidity ratio10.341g/kg
Supply relative humidity97.176%
Room sensible heat ratio70.588%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Room 24 °C 50 %, 35 + 8 kW, supply 13 °C. The inputs, in the units selected above:

InputValue
Room sensible load35.000 kW
Room latent load8.0000 kW
Room dry bulb24.000 °C
Room relative humidity50.000 %
Supply dry bulb13.000 °C
Barometric pressure (absolute)101.33 kPa

Applying the formula below gives:

ResultValue
Dry-air mass flow11,214 kg/h
Supply air volume (at the supply state)9,211.8 m³/h
Supply humidity ratio8.2911 g/kg
Supply relative humidity88.982 %
Room sensible heat ratio81.395 %

Open this example in the calculator and change any input.

Formula

\(\dot Q_s = \dot m_{da}(c_{pa} + W_s c_{pv})(T_r - T_s), \quad \dot Q_l = \dot m_{da}(W_r - W_s)\, h_g(T_r)\)

Variables

Symbol Meaning SI unit
\(\dot Q_s\) Room sensible load W
\(\dot Q_l\) Room latent load W
\(T_r\) Room dry bulb K
\(\varphi_r\) Room relative humidity -
\(T_s\) Supply dry bulb K
\(p\) Barometric pressure (absolute) Pa
\(\dot m_{da}\) Dry-air mass flow kg/s
\(\dot V_s\) Supply air volume (at the supply state) m³/s
\(W_s\) Supply humidity ratio kg/kg
\(\varphi_s\) Supply relative humidity -
\(SHR\) Room sensible heat ratio -

Method and standards

Energy and moisture balance on the room.

Where it is used

  • AHU and fan coil selection.
  • Control room and MCC room air conditioning.

Common mistakes

  • Volume at room instead of supply state.
  • Ignoring latent load.

Assumptions and limits

  • Steady state, perfect mixing.
  • The latent load is converted to moisture with the vapour enthalpy at room temperature, h_g = 2501 + 1.86 t kJ/kg (t in °C). Calculators that use 2501 kJ/kg alone (for example the sensible heat ratio and ADP calculator) give a supply humidity about 1–2 % different; both are common textbook forms.

References

  • Moist-air energy and moisture balances (ASHRAE Handbook—Fundamentals ch. 1 properties)

Questions and answers

35 kW sensible and 8 kW latent, room 24 °C 50 %, supply 13 °C?

About 3.1 kg/s of dry air, roughly 9,200 m³/h at the supply state.

Why does latent load change the supply humidity?

The supply air must be drier than the room by enough to absorb the moisture.

Supply RH above 100 %?

The chosen supply temperature cannot carry the latent load; lower it or add reheat.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators