Worked example
Example: 24 °C, 50 %, 30 + 8 kW, BF 0.1. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Room temperature | 24.000 °C |
| Room relative humidity | 50.000 % |
| Room sensible load | 30.000 kW |
| Room latent load | 8.0000 kW |
| Coil bypass factor | 10.000 % |
| Barometric pressure | 101.33 kPa |
Applying the formula below gives:
| Result | Value |
|---|---|
| Room sensible heat ratio | 0.78947 |
| Apparatus dew point | 10.341 °C |
| Supply air temperature | 11.707 °C |
| Supply humidity ratio | 7.9587 g/kg |
| Supply air flow | 7,017.0 m³/h |
Open this example in the calculator and change any input.
Formula
\(SHR = \frac{Q_s}{Q_s + Q_l}, \quad W_{sat}(t_{adp}) = W_r - \frac{Q_l}{Q_s}\frac{c_{pm}}{h_{fg}}(t_r - t_{adp}), \quad t_s = t_{adp} + BF(t_r - t_{adp})\)
\(c_{pm} = c_{p,a} + c_{p,v}W_r, \quad W_s = W_r - \frac{Q_l}{Q_s}\frac{c_{pm}}{h_{fg}}(t_r - t_s), \quad \dot V_s = \frac{Q_s}{c_{pm}(t_r - t_s)}\,v_s\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(t_r\) | Room temperature | K |
| \(\varphi_r\) | Room relative humidity | - |
| \(Q_s\) | Room sensible load | W |
| \(Q_l\) | Room latent load | W |
| \(BF\) | Coil bypass factor | - |
| \(p\) | Barometric pressure | Pa |
| \(SHR\) | Room sensible heat ratio | - |
| \(t_{adp}\) | Apparatus dew point | K |
| \(t_s\) | Supply air temperature | K |
| \(W_s\) | Supply humidity ratio | kg/kg |
| \(\dot V_s\) | Supply air flow | m³/s |
| \(W_r\) | Room humidity ratio | kg/kg |
| \(W_{sat}\) | Saturation humidity ratio | kg/kg |
| \(c_{pm}\) | Moist-air specific heat per kg dry air | J/(kg·K) |
| \(c_{p,a}\) | Dry-air specific heat, 1 006 | J/(kg·K) |
| \(c_{p,v}\) | Water-vapour specific heat, 1 860 | J/(kg·K) |
| \(h_{fg}\) | Latent heat used, 2 501 000 | J/kg |
| \(v_s\) | Specific volume of the supply air per kg dry air | m³/kg |
Method and standards
Room ratio line.
Where it is used
- Cooling coil selection.
- Checking whether a coil can hold room humidity.
Common mistakes
- Using grand SHR (with fresh air) for the room line.
- Ignoring bypass factor.
Assumptions and limits
- Room load only; no fan or duct gains.
- The latent load is converted with h_fg = 2 501 kJ/kg (the 0 °C value of the ASHRAE moist-air enthalpy) and c_pm = 1.006 + 1.86 W_r kJ/(kg·K). The supply air flow from room load calculator uses the vapour enthalpy at room temperature (about 2 545 kJ/kg), so the two give supply humidity ratios about 1.7 % apart for the same loads.
References
- ASHRAE Handbook—Fundamentals (2017)
- ch. 1 (moist-air processes); Carrier
- Handbook of Air Conditioning System Design (ADP and bypass factor method)
Questions and answers
What is the apparatus dew point?
The effective coil surface temperature: where the room ratio line meets the saturation curve.
Why does a low SHR need a cold coil?
More moisture must be removed per unit of cooling, so the ratio line is steeper and meets saturation at a lower temperature.
What do the defaults represent?
An office-type room at 24 °C and 50 % with a moderate latent share and a typical bypass factor.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.