Worked example
Example: Control room 0.05 m² at 15 Pa. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Total leakage area | 0.050000 m² |
| Pressure difference | 15.000 Pa |
| Discharge coefficient | 0.61000 - |
| Air density | 1.2000 kg/m³ |
| Room volume | 200.00 m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Leakage air flow | 549.00 m³/h |
| Leakage as air changes per hour | 2.7450 |
| Ideal jet velocity through the gaps √(2Δp/ρ) | 5.0000 m/s |
Open this example in the calculator and change any input.
Formula
\(v = \sqrt{\frac{2\Delta p}{\rho}}, \quad \dot V = C_dA_Lv, \quad ACH = \frac{3600\,\dot V}{V}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(A_L\) | Total leakage area | m² |
| \(\Delta p\) | Pressure difference | Pa |
| \(C_d\) | Discharge coefficient | - |
| \(\rho\) | Air density | kg/m³ |
| \(V\) | Room volume | m³ |
| \(\dot V\) | Leakage air flow | m³/s |
| \(ACH\) | Leakage as air changes per hour | - |
| \(v\) | Ideal jet velocity through the gaps | m/s |
Method and standards
Orifice equation.
Where it is used
- Control and MCC room pressurisation.
- Clean room supply excess.
Common mistakes
- Ignoring cable trenches and ducts.
- Designing to zero leakage.
Assumptions and limits
- Orifice flow; constant density.
- v is the ideal (vena contracta) jet velocity; the mean velocity over the leakage area A_L is C_d v.
References
- ASHRAE Handbook—Fundamentals (2017)
- ch. 16 (orifice equation for leakage); ASHRAE Handbook—HVAC Applications (2019)
- ch. 19 (clean spaces)
Questions and answers
Why pressurise a room?
To keep dust, fumes or corrosive gases out of control rooms, MCC rooms and clean areas.
How much pressure is enough?
Typically 10–15 Pa between clean areas, 25–50 Pa for stair cores in fire mode.
What do the defaults represent?
A control room with door and cable gaps held at 15 Pa.