Worked example
Example: 1.5 kW panel at 55/45/20 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Rated output | 1,500.0 W |
| Rated temperature difference (EN 442: 50 K) | 50.000 K |
| Radiator exponent | 1.3000 - |
| Flow temperature | 55.000 °C |
| Return temperature | 45.000 °C |
| Room temperature | 20.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Log-mean temperature difference | 29.720 K |
| Actual output | 762.77 W |
| Output factor | 50.852 % |
| Water flow | 65.599 kg/h |
Open this example in the calculator and change any input.
Formula
\(\Delta T_{ln} = \frac{t_f - t_r}{\ln\frac{t_f - t_a}{t_r - t_a}}, \quad Q = Q_n\left(\frac{\Delta T_{ln}}{\Delta T_n}\right)^n, \quad \dot m = \frac{Q}{c_w (t_f - t_r)}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q_n\) | Rated output | W |
| \(\Delta T_n\) | Rated temperature difference (EN 442: 50 K) | K |
| \(n\) | Radiator exponent | - |
| \(t_f\) | Flow temperature | K |
| \(t_r\) | Return temperature | K |
| \(t_a\) | Room temperature | K |
| \(\Delta T_{ln}\) | Log-mean temperature difference | K |
| \(Q\) | Actual output | W |
| \(Q/Q_n\) | Output factor | - |
| \(\dot m\) | Water flow | kg/s |
| \(c_w\) | Specific heat of water, 4 186 | J/(kg·K) |
Method and standards
EN 442 characteristic.
Where it is used
- Heat pump retrofits.
- Checking emitters at lower flow temperatures.
Common mistakes
- Using arithmetic mean temperature at low ΔT ratios.
- Ignoring the exponent.
Assumptions and limits
- Steady output; rated exponent.
References
- EN 442-2 characteristic equation Q = K_mΔT^n with the logarithmic temperature difference
Questions and answers
Why does a radiator give less at heat-pump temperatures?
At 55/45/20 °C the log-mean difference is about 30 K instead of 50 K; with n = 1.3 output falls to about half.
Why use the logarithmic difference?
Water cools along the radiator; the log-mean difference is what the rating method uses.
What do the defaults represent?
A 1.5 kW (rated) panel radiator run at 55/45 °C in a 20 °C room.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.