Worked example
Example: Two pumps, both in the room. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Motor rated output | 15.000 kW |
| Load factor (share of rated output) | 80.000 % |
| Use factor (share of time running) | 100.00 % |
| Motor efficiency at that load | 91.000 % |
| Arrangement | Motor and driven machine in the room |
| Number of such motors | 2.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Heat per motor | 13.187 kW |
| Total heat to the room | 26.374 kW |
Open this example in the calculator and change any input.
Formula
\(\dot Q = \frac{P_r F_{LM} F_{UM}}{\eta_m}, \quad P_r F_{LM} F_{UM}, \quad P_r F_{LM} F_{UM}\frac{1 - \eta_m}{\eta_m}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P_r\) | Motor rated output | W |
| \(F_{LM}\) | Load factor (share of rated output) | - |
| \(F_{UM}\) | Use factor (share of time running) | - |
| \(\eta_m\) | Motor efficiency at that load | - |
| \(\text{arrangement}\) | Arrangement | - |
| \(n\) | Number of such motors | - |
| \(\dot Q_1\) | Heat per motor | W |
| \(\dot Q\) | Total heat to the room | W |
Method and standards
Energy balance.
Where it is used
- Pump houses, compressor rooms and MCC rooms.
- Ventilation sizing.
Common mistakes
- Nameplate without load factor.
- Wrong arrangement.
Assumptions and limits
- Steady running.
References
- Motor heat gain for the three arrangements
- P/η
- P and P(1 − η)/η (ASHRAE Handbook—Fundamentals ch. 18)
Questions and answers
Two 15 kW pumps at 80 % load, 91 % efficient, both in the room?
About 26 kW of heat.
Motor inside, pump outside?
Only the losses: about 2.4 kW.
Why does a pump's work end as heat?
Unless it leaves with the fluid, the machine's work is dissipated in the room.