FireCADCalc

Heat Recovery Wheel or Plate Exchanger Saving

Supply air temperature and sensible heat recovered by a heat wheel or plate heat exchanger between fresh air and exhaust air, with the energy saved in a year.

Fan and blowerAir conditioning and chillers

Inputs

Examples: Summer 10 000 m³/h, 40 °C outside, 24 °C exhaust, 70 %, 3 000 hWinter 20 000 m³/h, -5 °C outside, 21 °C exhaust, 75 %, 2 500 hPlate exchanger 5 000 m³/h, 35 °C, 26 °C, 55 %, 4 000 h

Results

Sensible recovery only, equal supply and exhaust flows; an enthalpy wheel also recovers moisture. Fan power for the extra pressure drop is not deducted.

Fresh air temperature after the recovery unit30.050°C
Dry air flow5,592.8kg/h
Sensible heat recovered (heating or cooling)7.9508kW
Energy recovered per year31,803kWh

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Summer 10 000 m³/h, 40 °C outside, 24 °C exhaust, 70 %, 3 000 h. The inputs, in the units selected above:

InputValue
Fresh (outdoor) air flow10,000 m³/h
Atmospheric pressure101.33 kPa
Outdoor air temperature40.000 °C
Outdoor air humidity ratio12.000 g/kg
Exhaust (room) air temperature24.000 °C
Sensible effectiveness (equal air flows)70.000 %
Running hours per year at this condition3,000.0 h

Applying the formula below gives:

ResultValue
Fresh air temperature after the recovery unit28.800 °C
Dry air flow11,059 kg/h
Sensible heat recovered (heating or cooling)35.380 kW
Energy recovered per year106,141 kWh

Open this example in the calculator and change any input.

Formula

\(T_s = T_o + \varepsilon (T_r - T_o)\)

\(Q_r = \dot m_a |h(T_s, W_o) - h(T_o, W_o)|\)

\(E = Q_r t_y\)

Variables

Symbol Meaning SI unit
\(Q\) fresh air flow m³/s
\(p\) atmospheric pressure Pa
\(T_o\) outdoor temperature K
\(W_o\) outdoor humidity ratio kg/kg
\(T_r\) exhaust temperature K
\(\varepsilon\) sensible effectiveness -
\(t_y\) hours per year s
\(h\) moist air enthalpy (ASHRAE) J/kg
\(T_s\) fresh air temperature after recovery K
\(\dot m_a\) dry air flow kg/s
\(Q_r\) heat recovered W
\(E\) energy per year J

Method and standards

Sensible effectiveness is the fraction of the possible temperature change achieved; with equal flows the supply leaves at T_o + ε (T_r − T_o). The heat recovered is the dry air flow times the enthalpy change at constant humidity.

Where it is used

  • Evaluating heat recovery on fresh-air units.
  • Estimating payback of a wheel or plate exchanger.
  • Comparing recovery devices.

Common mistakes

  • Counting recovery when outdoor air is already near room temperature.
  • Ignoring the added fan power.
  • Using total effectiveness for a sensible-only device.

Assumptions and limits

  • Equal supply and exhaust flows; sensible only. An outdoor humidity ratio above saturation is flagged.

References

  • Sensible effectiveness definition
  • ASHRAE psychrometrics

Questions and answers

What does a 70 % wheel recover on 10 000 m³/h of 40 °C fresh air with 24 °C exhaust?

It cools the fresh air to about 28.8 °C, saving about 35 kW of sensible cooling.

Does it work in winter too?

Yes: the same wheel preheats cold fresh air from the warm exhaust.

What about humidity?

This is sensible recovery only; an enthalpy wheel also transfers moisture and saves more in humid climates.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.