Worked example
Example: AHU 20 000 m³/h, motor in the stream. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Air flow | 20,000 m³/h |
| Fan total pressure rise | 101.97 mmWC |
| Fan efficiency | 70.000 % |
| Motor efficiency | 92.000 % |
| Motor position | In the air stream |
| Air density | 1.2000 kg/m³ |
| Air specific heat | 1.0060 kJ/(kg·K) |
Applying the formula below gives:
| Result | Value |
|---|---|
| Shaft power | 7.9365 kW |
| Motor input | 8.6266 kW |
| Heat to the air | 8.6266 kW |
| Air temperature rise | 1.2863 K |
Open this example in the calculator and change any input.
Formula
\(P_s = \frac{\dot V \Delta p_t}{\eta_f}, \quad P_e = \frac{P_s}{\eta_m}, \quad \dot Q = P_e\ \text{(motor in the air stream)}\ \text{or}\ P_s\ \text{(motor outside)}, \quad \Delta T = \frac{\dot Q}{\rho c_p \dot V}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V\) | Air flow | m³/s |
| \(\Delta p_t\) | Fan total pressure rise | Pa |
| \(\eta_f\) | Fan efficiency | - |
| \(\eta_m\) | Motor efficiency | - |
| \(\text{motor}\) | Motor position | - |
| \(\rho\) | Air density | kg/m³ |
| \(c_p\) | Air specific heat | J/(kg·K) |
| \(P_s\) | Shaft power | W |
| \(P_e\) | Motor input | W |
| \(\dot Q\) | Heat to the air | W |
| \(\Delta T\) | Air temperature rise | K |
Method and standards
Energy balance.
Where it is used
- AHU and ID/FD fan air temperature rise.
- Cooling load completeness.
Common mistakes
- Using static instead of total pressure.
- Forgetting the motor in the stream.
Assumptions and limits
- Steady state.
References
- Energy balance: shaft power = V Δp / η_f
- all dissipated in the air (ASHRAE Handbook—Fundamentals ch. 18)
Questions and answers
20,000 m³/h at 1000 Pa, 70 % fan, motor in the stream?
About 8.6 kW to the air: a rise of about 1.3 K.
Draw-through or blow-through?
Blow-through adds the heat before the coil, draw-through after it, changing the supply temperature.
Why include it?
On large AHUs it is several per cent of the cooling load.