Worked example
Example: Heating with oil. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Heat loss coefficient (fabric and ventilation) | 2.5000 kW/K |
| Degree-days (K·day) | 2,200.0 - |
| System efficiency (heating, NCV basis) or COP (cooling) | 0.85000 - |
| Fuel net calorific value (0 for electricity) | 42.000 MJ/kg |
| Price per kg of fuel or per kWh | 75.000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Heat or cooling delivered | 132,000 kWh |
| Energy input | 155,294 kWh |
| Fuel (if NCV given) | 13,311 kg |
| Cost | 998,319 |
Open this example in the calculator and change any input.
Formula
\(Q = UA \cdot DD \cdot 86\,400, \quad E = \frac{Q}{\eta}, \quad m_f = \frac{E}{NCV}, \quad C = m_f\,c\ \ \text{(fuel)}\ \text{or}\ C = \frac{E}{3.6\times10^6}\,c\ \ \text{(electricity, per kWh)}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(UA\) | Heat loss coefficient (fabric and ventilation) | W/K |
| \(DD\) | Degree-days (K·day) | - |
| \(\eta\) | System efficiency (heating, NCV basis) or COP (cooling) | - |
| \(NCV\) | Fuel net calorific value (0 for electricity) | J/kg |
| \(c\) | Price per kg of fuel or per kWh | - |
| \(Q\) | Heat or cooling delivered | J |
| \(E\) | Energy input | J |
| \(m_f\) | Fuel (if NCV given) | kg |
| \(C\) | Cost | - |
Method and standards
Degree-day method.
Where it is used
- Fuel budgets for heating colonies and offices.
- Comparing insulation options.
Common mistakes
- Wrong base temperature.
- Mixing heating and cooling days.
Assumptions and limits
- Steady UA.
- The fuel quantity uses the net calorific value, so the heating efficiency must be on the NCV basis too; a GCV-based efficiency mis-states the fuel by the GCV/NCV ratio (about 5–11 %).
References
- Degree-day method Q = UA × DD × 24 h (CIBSE TM41; ASHRAE Handbook—Fundamentals ch. 19)
Questions and answers
UA 2500 W/K and 2200 K·day?
132,000 kWh of heat; at 85 % that is about 13,311 kg of fuel oil.
Cooling?
Use cooling degree-days and the chiller COP as the efficiency, with NCV 0 for electricity.
Why does the base temperature matter?
Internal and solar gains supply the first few degrees.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.