Worked example
Example: 25 people, 1000 ppm. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Number of people | 25.000 - |
| CO₂ generation per person | 0.005200 L/s |
| Indoor CO₂ limit (ppm) | 1,000.0 - |
| Outdoor CO₂ (ppm) | 420.00 - |
| Actual outdoor air flow (for the steady level) | 200.00 L/s |
Applying the formula below gives:
| Result | Value |
|---|---|
| Outdoor air needed | 224.14 L/s |
| Per person | 8.9655 L/s |
| Steady CO₂ with the actual flow (ppm) | 1,070.0 |
Open this example in the calculator and change any input.
Formula
\(\dot V = \frac{n G}{(C_i - C_o)\times10^{-6}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(n\) | Number of people | - |
| \(G\) | CO₂ generation per person | m³/s |
| \(C_i\) | Indoor CO₂ limit (ppm) | - |
| \(C_o\) | Outdoor CO₂ (ppm) | - |
| \(\dot V_a\) | Actual outdoor air flow (for the steady level) | m³/s |
| \(\dot V\) | Outdoor air needed | m³/s |
| \(\dot V/n\) | Per person | m³/s |
| \(C_{ss}\) | Steady CO₂ with the actual flow (ppm) | - |
Method and standards
Mass balance.
Where it is used
- Control rooms, offices and meeting rooms.
- Demand-controlled ventilation set points.
Common mistakes
- ppm used as a fraction.
- Ignoring outdoor CO₂.
Assumptions and limits
- Perfect mixing, steady state.
- The steady CO₂ is shown only for an actual flow above zero.
References
- Steady-state mass balance V = n G/(C_i − C_o)
Questions and answers
25 people, 1000 ppm limit, 420 outdoors?
About 224 L/s, 9.0 L/s per person.
Why use CO₂?
It tracks occupancy and is easy to measure.
Short meetings?
CO₂ takes time to build up; the steady value is the upper bound.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.