Car Park Ventilation for Carbon Monoxide

Ventilation air flow for an enclosed car park to keep carbon monoxide below a limit from moving cars and their emission rate, with air changes.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 40 cars, 180 g/h each, 35 ppmMall basement 150 cars, 60 g/h, 25 ppm

Results

Steady-state dilution with perfect mixing. Emission per car depends on the fleet and whether engines are cold; modern cars emit far less than older design figures. Many codes also set a minimum air change rate; use the larger.

CO generation9,000.0g/h
Allowed rise above outdoor27.477mg/m³
Ventilation air flow327,545m³/h
Air changes per hour5.4591

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 40 cars, 180 g/h each, 35 ppm. The inputs, in the units selected above:

InputValue
Cars moving at the peak40.000 -
CO emission per moving car180.00 g/h
CO limit35.000 ppm
CO in outdoor air2.0000 ppm
Air temperature20.000 °C
Car park volume15,000 m³

Applying the formula below gives:

ResultValue
CO generation7,200.0 g/h
Allowed rise above outdoor38.426 mg/m³
Ventilation air flow187,376 m³/h
Air changes per hour12.492

Open this example in the calculator and change any input.

Formula

\(\dot V = \frac{NE}{(C_{lim} - C_o)\rho_{CO}}, \quad \rho_{CO} = \frac{pM_{CO}}{RT}\)

Variables

Symbol Meaning SI unit
\(N\) Cars moving at the peak -
\(E\) CO emission per moving car kg/s
\(C_{lim}\) CO limit -
\(C_o\) CO in outdoor air -
\(T\) Air temperature K
\(p\) Air pressure, standard atmosphere 101 325 Pa Pa
\(M_{CO}\) Molar mass of CO, 28.010 kg/kmol kg/kmol
\(R\) Universal gas constant, 8 314.462 618 J/(kmol·K) J/(kmol·K)
\(\rho_{CO}\) Density of pure CO at p and T kg/m³
\(V\) Car park volume m³
\(G\) CO generation kg/s
\(\Delta C\) Allowed rise above outdoor kg/m³
\(\dot V\) Ventilation air flow m³/s
\(ACH\) Air changes per hour -

Method and standards

Steady dilution.

Where it is used

  • Basement car parks in commercial buildings.
  • Loading bays.

Common mistakes

  • Using old fleet emission factors.
  • Ignoring short-circuiting between supply and exhaust.

Assumptions and limits

  • Well mixed; steady state.
  • The ppm-to-mass conversion is at one standard atmosphere (101 325 Pa).

References

  • ASHRAE Handbook—HVAC Applications (2019)
  • ch. 16 (enclosed vehicular facilities: dilution of CO)

Questions and answers

Why CO and not other exhaust gases?

CO is the traditional design pollutant for petrol vehicles; diesel fleets may need NO₂ as well.

Can demand control save energy?

Yes: CO sensors let fans run slow most of the day and full only at peaks.

What do the defaults represent?

40 cars moving at once in a basement car park with a 35 ppm limit.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.