Building Fabric Heat Loss (U × A × ΔT)

Heat loss or gain through walls, roof, floor and windows from U-values, areas and the indoor–outdoor temperature difference, with the yearly energy from degree-days.

Air conditioning and chillers

Inputs

Examples: Office 300/200/200/60 m², 21 °C in, 5 °C out, 1 500 K·dayControl room, cooling: 45 °C out, 24 °C in, no degree-daysWarehouse 1 200 / 2 000 / 2 000 / 50 m², 15 °C in, 0 °C out, 2 500 K·day

U-values

Areas

Results

Fabric only: add ventilation and infiltration (see the ventilation heat load calculator) and thermal bridges for the full load.

Through the walls2.8800kW
Through the roof1.2800kW
Through the floor1.6000kW
Through the windows2.6880kW
Total fabric heat loss (negative = heat gain)8.4480kW
Fabric heat loss coefficient0.52800kW/K
Seasonal fabric heat loss19,008kWh

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Office 300/200/200/60 m², 21 °C in, 5 °C out, 1 500 K·day. The inputs, in the units selected above:

InputValue
U-value of the walls0.60000 W/(m²·K)
U-value of the roof0.40000 W/(m²·K)
U-value of the floor0.50000 W/(m²·K)
U-value of the windows2.8000 W/(m²·K)
Area of the walls300.00 m²
Area of the roof200.00 m²
Area of the floor200.00 m²
Area of the windows60.000 m²
Indoor temperature21.000 °C
Outdoor design temperature5.0000 °C
Degree-days for the season (K·day, 0 = none)1,500.0 -

Applying the formula below gives:

ResultValue
Through the walls2.8800 kW
Through the roof1.2800 kW
Through the floor1.6000 kW
Through the windows2.6880 kW
Total fabric heat loss (negative = heat gain)8.4480 kW
Fabric heat loss coefficient0.52800 kW/K
Seasonal fabric heat loss19,008 kWh

Open this example in the calculator and change any input.

Formula

\(Q_i = U_i A_i (T_i - T_o)\)

\(\Sigma UA = \sum U_i A_i, \quad Q = \Sigma UA\, (T_i - T_o)\)

\(E = \Sigma UA \cdot DD \cdot 86\,400\ \text{s}\)

Variables

Symbol Meaning SI unit
\(U_1\) U-value of walls W/(m²·K)
\(U_2\) U-value of roof W/(m²·K)
\(U_3\) U-value of floor W/(m²·K)
\(U_4\) U-value of windows W/(m²·K)
\(A_1\) wall area m²
\(A_2\) roof area m²
\(A_3\) floor area m²
\(A_4\) window area m²
\(U_i\) U-value of element i W/(m²·K)
\(A_i\) area of element i m²
\(T_i\) indoor temperature K
\(T_o\) outdoor temperature K
\(DD\) degree-days K·day
\(Q_1\) through walls W
\(Q_2\) through roof W
\(Q_3\) through floor W
\(Q_4\) through windows W
\(Q_i\) through element i W
\(Q\) Total fabric heat loss (negative = heat gain) W
\(\Sigma UA\) fabric heat loss coefficient W/K
\(E\) seasonal fabric heat loss J

Method and standards

Steady conduction through each element is U A ΔT; the sum gives the fabric load. Seasonal energy uses degree-days, the sum over the season of the daily temperature difference below the base temperature.

Where it is used

  • Sizing heating for offices, control rooms and workshops.
  • Comparing insulation upgrades.
  • Estimating seasonal heating energy.

Common mistakes

  • Using centre-of-panel U-values and ignoring thermal bridges.
  • Forgetting ventilation and infiltration.
  • Using degree-days to a different base temperature.

Assumptions and limits

  • Steady state; no solar or internal gains; fabric only.
  • When outdoor is warmer than indoor the losses come out negative (gains). The seasonal energy is ΣUA times whatever degree-days you enter: heating degree-days for heating, cooling degree-days for cooling.

References

  • Steady-state conduction Q = U A ΔT
  • Degree-day method

Questions and answers

What is the fabric loss of the example office?

8.4 kW at 16 K difference: UA 528 W/K across walls, roof, floor and windows; 1 500 degree-days give about 19 000 kWh a season.

Why are windows so important?

Their U-value is several times a wall's; in the example 60 m² of glass loses nearly as much as 300 m² of wall.

Does this work for cooling?

Yes for conduction: a negative result is a heat gain. Add solar and internal gains for a cooling load.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.