Worked example
Example: 500 m³/d, BOD 300, COD 600 mg/L, 250 m³ tank. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Wastewater flow | 500.00 m³/d |
| BOD concentration | 300.00 mg/L |
| COD concentration | 600.00 mg/L |
| Reactor (tank) volume | 250.00 m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| BOD load Q × BOD | 150.00 kg/d |
| COD load Q × COD | 300.00 kg/d |
| Organic loading rate (BOD) on the volume | 0.60000 kg/(m³·d) |
| Organic loading rate (COD) on the volume | 1.2000 kg/(m³·d) |
| COD to BOD ratio | 2.0000 |
Open this example in the calculator and change any input.
Formula
\(L = Q\, C, \quad OLR = \frac{L}{V}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | Wastewater flow | m³/s |
| \(BOD\) | BOD concentration | kg/m³ |
| \(COD\) | COD concentration | kg/m³ |
| \(V\) | Reactor (tank) volume | m³ |
| \(L_{BOD}\) | BOD load Q × BOD | kg/s |
| \(L_{COD}\) | COD load Q × COD | kg/s |
| \(OLR_{BOD}\) | Organic loading rate (BOD) on the volume | kg/(m³·s) |
| \(OLR_{COD}\) | Organic loading rate (COD) on the volume | kg/(m³·s) |
| \(COD/BOD\) | COD to BOD ratio | - |
Method and standards
Mass flow equals flow times concentration.
Where it is used
- ETP and STP design.
- Consent applications.
- Plant monitoring.
Common mistakes
- Unit slips between mg/L and kg/m³.
- Using peak flow with average concentration.
Assumptions and limits
- Average values.
References
- Metcalf & Eddy
- Wastewater Engineering (load = flow × concentration)
Questions and answers
What load does 500 m³/d at BOD 300 mg/L carry?
150 kg BOD per day (300 kg COD at 600 mg/L); on a 250 m³ tank, 0.6 kg BOD/(m³·d).
Why is mg/L × m³/d ÷ 1000 kg/d?
1 mg/L = 1 g/m³.
What does COD/BOD tell?
Around 2 suggests biodegradable waste; much higher means hard-to-treat organics.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.