Worked example
Example: Hard well water. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Free CO₂ (mg/L as CO₂) | 15.000 - |
| Bicarbonate alkalinity (mg/L as CaCO₃) | 200.00 - |
| Magnesium hardness (mg/L as CaCO₃) | 60.000 - |
| Total hardness (mg/L as CaCO₃) | 280.00 - |
| Excess lime (mg/L as CaCO₃) | 35.000 - |
| Lime purity as Ca(OH)₂ | 90.000 % |
| Soda ash purity | 98.000 % |
| Water flow | 2,000.0 m³/d |
Applying the formula below gives:
| Result | Value |
|---|---|
| Lime as Ca(OH)₂ (product, mg/L) | 270.71 |
| Soda ash (product, mg/L) | 86.446 |
| Lime per day | 541.42 kg/d |
| Soda ash per day | 172.89 kg/d |
Open this example in the calculator and change any input.
Formula
\(L_{CaCO_3} = CO_2\frac{100}{44} + Alk + Mg + X, \quad S_{CaCO_3} = TH - Alk\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(CO_2\) | Free CO₂ (mg/L as CO₂) | - |
| \(Alk\) | Bicarbonate alkalinity (mg/L as CaCO₃) | - |
| \(Mg\) | Magnesium hardness (mg/L as CaCO₃) | - |
| \(TH\) | Total hardness (mg/L as CaCO₃) | - |
| \(X\) | Excess lime (mg/L as CaCO₃) | - |
| \(p_L\) | Lime purity as Ca(OH)₂ | - |
| \(p_S\) | Soda ash purity | - |
| \(\dot V\) | Water flow | m³/s |
| \(d_L\) | Lime as Ca(OH)₂ (product, mg/L) | - |
| \(d_S\) | Soda ash (product, mg/L) | - |
| \(\dot m_L\) | Lime per day | kg/s |
| \(\dot m_S\) | Soda ash per day | kg/s |
Method and standards
Stoichiometry in CaCO₃ equivalents.
Where it is used
- Clarifier pre-treatment for boiler and cooling water.
- Examinations.
Common mistakes
- Mixing 'as ion' and 'as CaCO₃' units.
- Forgetting CO₂.
Assumptions and limits
- Complete reactions. Mg above TH is flagged; with alkalinity above total hardness the lime term still takes the full alkalinity (sodium bicarbonate waters) and the soda ash is zero.
- Molar masses CaCO₃ 100.0869, CO₂ 44.0095, Ca(OH)₂ 74.0927, Na₂CO₃ 105.9888 g/mol.
References
- Lime–soda softening stoichiometry in CaCO₃ equivalents: lime = CO₂ + HCO₃⁻ + Mg²⁺ + excess; soda ash = non-carbonate hardness
Questions and answers
15 mg/L CO₂, 200 alkalinity, 60 Mg, 280 TH, 35 excess?
About 271 mg/L of 90 % lime and 86 mg/L of soda ash.
Why excess lime?
To raise pH enough to precipitate Mg(OH)₂.
Recarbonation?
Needed afterwards to bring pH down and stabilise the water.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.