Worked example
Example: Three-gas example mixture. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Gas 1 share of the flammable part | 80.000 % |
| Gas 1 LFL | 5.0000 % |
| Gas 1 UFL | 15.000 % |
| Gas 2 share | 15.000 % |
| Gas 2 LFL | 3.0000 % |
| Gas 2 UFL | 12.400 % |
| Gas 3 share | 5.0000 % |
| Gas 3 LFL | 2.1000 % |
| Gas 3 UFL | 9.5000 % |
| Gas 4 share (0 = none) | 0 % |
| Gas 4 LFL | 4.0000 % |
| Gas 4 UFL | 75.000 % |
| Flammable share of the whole gas | 100.00 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Lower flammability limit of the flammable mixture | 4.2770 % |
| Upper flammability limit (approximate) | 14.146 % |
| LFL of the whole gas (inerts included) | 4.2770 % |
Open this example in the calculator and change any input.
Formula
\(LFL_{mix} = \frac{1}{\sum_i y_i/LFL_i}, \quad UFL_{mix} \approx \frac{1}{\sum_i y_i/UFL_i}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(y_1\) | Gas 1 share of the flammable part | - |
| \(LFL_1\) | Gas 1 LFL | - |
| \(UFL_1\) | Gas 1 UFL | - |
| \(y_2\) | Gas 2 share | - |
| \(LFL_2\) | Gas 2 LFL | - |
| \(UFL_2\) | Gas 2 UFL | - |
| \(y_3\) | Gas 3 share | - |
| \(LFL_3\) | Gas 3 LFL | - |
| \(UFL_3\) | Gas 3 UFL | - |
| \(y_4\) | Gas 4 share (0 = none) | - |
| \(LFL_4\) | Gas 4 LFL | - |
| \(UFL_4\) | Gas 4 UFL | - |
| \(\phi_f\) | Flammable share of the whole gas | - |
| \(LFL_{mix}\) | Lower flammability limit of the flammable mixture | - |
| \(UFL_{mix}\) | Upper flammability limit (approximate) | - |
| \(LFL_{gas}\) | LFL of the whole gas (inerts included) | - |
Method and standards
Le Chatelier's rule as in Perry's Eq. (23-1).
Where it is used
- Gas detector set points.
- Purge and dilution design.
Common mistakes
- Including inerts in the shares.
- Using limits at another temperature.
Assumptions and limits
- Near-ambient conditions; similar flammable gases.
- Shares adding up to 99–101 % are normalised to 100 %.
- Screening estimate: the whole-gas LFL with inerts is given, but no whole-gas UFL, since inerts narrow the range in a way this rule does not capture.
References
- Perry's Chemical Engineers' Handbook
- 9th ed. (McGraw-Hill, 2019)
- sec. 23 (process safety)
- Eq. (23-1): Le Chatelier's mixing rule
Questions and answers
What does the rule assume?
Each component contributes in proportion to its share divided by its own LFL; it works well for similar hydrocarbons.
What about inert gases?
Treat them separately: the whole-gas LFL is the flammable mixture's LFL divided by the flammable share.
Is the UFL rule as good?
No; it is a rough estimate.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.