FireCADCalc

Flammability Limits of a Gas Mixture (Le Chatelier)

Lower and upper flammability limits of a mixture of up to four flammable gases from each one's limits and share of the flammable part (Le Chatelier).

Thermal power plantDistillery and ethanolRefinery and petrochemicalChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: Three-gas example mixtureWith 40 % inerts

Results

Inerts raise the whole-gas LFL as shown, but also narrow the range; no whole-gas UFL is given because inerts change it in a way this rule does not capture. The UFL rule is less reliable than the LFL rule. Use measured limits from the SDS or Perry's sec. 23 tables.

Lower flammability limit of the flammable mixture4.2770%
Upper flammability limit (approximate)14.146%
LFL of the whole gas (inerts included)4.2770%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Three-gas example mixture. The inputs, in the units selected above:

InputValue
Gas 1 share of the flammable part80.000 %
Gas 1 LFL5.0000 %
Gas 1 UFL15.000 %
Gas 2 share15.000 %
Gas 2 LFL3.0000 %
Gas 2 UFL12.400 %
Gas 3 share5.0000 %
Gas 3 LFL2.1000 %
Gas 3 UFL9.5000 %
Gas 4 share (0 = none)0 %
Gas 4 LFL4.0000 %
Gas 4 UFL75.000 %
Flammable share of the whole gas100.00 %

Applying the formula below gives:

ResultValue
Lower flammability limit of the flammable mixture4.2770 %
Upper flammability limit (approximate)14.146 %
LFL of the whole gas (inerts included)4.2770 %

Open this example in the calculator and change any input.

Formula

\(LFL_{mix} = \frac{1}{\sum_i y_i/LFL_i}, \quad UFL_{mix} \approx \frac{1}{\sum_i y_i/UFL_i}\)

Variables

Symbol Meaning SI unit
\(y_1\) Gas 1 share of the flammable part -
\(LFL_1\) Gas 1 LFL -
\(UFL_1\) Gas 1 UFL -
\(y_2\) Gas 2 share -
\(LFL_2\) Gas 2 LFL -
\(UFL_2\) Gas 2 UFL -
\(y_3\) Gas 3 share -
\(LFL_3\) Gas 3 LFL -
\(UFL_3\) Gas 3 UFL -
\(y_4\) Gas 4 share (0 = none) -
\(LFL_4\) Gas 4 LFL -
\(UFL_4\) Gas 4 UFL -
\(\phi_f\) Flammable share of the whole gas -
\(LFL_{mix}\) Lower flammability limit of the flammable mixture -
\(UFL_{mix}\) Upper flammability limit (approximate) -
\(LFL_{gas}\) LFL of the whole gas (inerts included) -

Method and standards

Le Chatelier's rule as in Perry's Eq. (23-1).

Where it is used

  • Gas detector set points.
  • Purge and dilution design.

Common mistakes

  • Including inerts in the shares.
  • Using limits at another temperature.

Assumptions and limits

  • Near-ambient conditions; similar flammable gases.
  • Shares adding up to 99–101 % are normalised to 100 %.
  • Screening estimate: the whole-gas LFL with inerts is given, but no whole-gas UFL, since inerts narrow the range in a way this rule does not capture.

References

  • Perry's Chemical Engineers' Handbook
  • 9th ed. (McGraw-Hill, 2019)
  • sec. 23 (process safety)
  • Eq. (23-1): Le Chatelier's mixing rule

Questions and answers

What does the rule assume?

Each component contributes in proportion to its share divided by its own LFL; it works well for similar hydrocarbons.

What about inert gases?

Treat them separately: the whole-gas LFL is the flammable mixture's LFL divided by the flammable share.

Is the UFL rule as good?

No; it is a rough estimate.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...