Worked example
Example: 10 m³/h, 200 mg/L, 12 h run, capacity 50 g/L, salt 160 g/L. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Water flow | 10.000 m³/h |
| Total hardness of the raw water, as CaCO₃ | 200.00 mg/L |
| Run time between regenerations | 12.000 h |
| Operating capacity of the resin, as CaCO₃ | 50.000 g/L |
| Salt dose per litre of resin | 160.00 g/L |
| Installed resin volume (for its run length) | 0.50000 m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Resin volume needed | 480.00 L |
| Salt per regeneration | 76.800 kg |
| Hardness removed per run, as CaCO₃ | 24.000 kg |
| Run length of the installed resin | 12.500 h |
Open this example in the calculator and change any input.
Formula
\(L_h = \dot V\,t_r\,H \qquad V_r = \frac{L_h}{C_r} \qquad m_s = V_r\,s \qquad t_i = \frac{V_i\,C_r}{\dot V\,H}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V\) | water flow | m³/s |
| \(H\) | total hardness as CaCO₃ | kg/m³ |
| \(t_r\) | run time between regenerations | s |
| \(C_r\) | resin operating capacity as CaCO₃ | kg/m³ |
| \(s\) | salt dose per volume of resin | kg/m³ |
| \(V_i\) | installed resin volume | m³ |
| \(V_r\) | resin volume needed | m³ |
| \(m_s\) | salt per regeneration | kg |
| \(L_h\) | hardness removed per run | kg |
| \(t_i\) | run length of the installed resin | s |
Method and standards
Mass balance of an ion-exchange bed: the hardness load per run equals the resin volume times its operating capacity. Capacity and salt dose are the resin maker's data.
Where it is used
- Sizing softeners for boiler make-up in process plants.
- Checking regeneration frequency after a change in raw water.
- Salt budgets.
Common mistakes
- Using the total (theoretical) capacity instead of the operating capacity.
- Forgetting the regeneration downtime when there is only one vessel.
- Using hardness in mg/L as Ca, not as CaCO₃.
Assumptions and limits
- Constant flow and hardness; no hardness leakage; capacity at your salt dose.
- No design margin, minimum bed depth or regeneration downtime is included: add a margin on the resin, check the bed depth with the maker, and provide a second unit or storage for the regeneration time.
References
- Ion-exchange mass balance (hardness load / operating capacity)
Questions and answers
How much resin does a softener need?
The hardness it removes per run divided by the resin's capacity. 10 m³/h of water at 200 mg/L hardness for 12 hours is 24 kg of hardness as CaCO₃; at 50 g/L capacity that is 480 L of resin and 77 kg of salt per regeneration at 160 g/L.
Where does the capacity come from?
The resin maker's curve: capacity rises with the salt dose but salt efficiency falls. 40–60 g/L as CaCO₃ is common for strong-acid cation resin; use the maker's figure for your salt dose.
How long will my existing softener run?
Enter the installed resin volume: 0.5 m³ at 50 g/L treating 10 m³/h of 200 mg/L water runs 12.5 hours.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.