Feedwater pH from Ammonia Dose (and Dose for a pH)

pH at 25 °C of pure water dosed with ammonia, the share present as free NH₃, and the ammonia needed for a target feedwater pH, from the ammonium equilibrium.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserWater treatment plantDeaerator and feedwater system

Inputs

Examples: 0.5 mg/L NH3, target pH 9.32 mg/L NH3, target pH 9.60.2 mg/L NH3, target pH 9.0

Results

Pure water with ammonia only, at 25 °C; carbon dioxide, other amines and salts change the result. pH is measured on a cooled sample at 25 °C.

pH at 25 °C from the dose9.5745
Share of the ammonia present as free NH₃68.036%
Ammonia needed for the target pH, as NH₃2.2086mg/L
pKa of ammonium at 25 °C9.2464

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 0.5 mg/L NH3, target pH 9.3. The inputs, in the units selected above:

InputValue
Ammonia in the water, as NH₃0.50000 mg/L
Target pH at 25 °C9.3000 -

Applying the formula below gives:

ResultValue
pH at 25 °C from the dose9.1927
Share of the ammonia present as free NH₃46.915 %
Ammonia needed for the target pH, as NH₃0.72427 mg/L
pKa of ammonium at 25 °C9.2464

Open this example in the calculator and change any input.

Formula

\(pK_a = 0.09018 + \frac{2729.92}{T}, \quad T = 298.15\ \text{K}\)

\([\text{H}^+] + \frac{c\,[\text{H}^+]}{[\text{H}^+] + K_a} = \frac{K_w}{[\text{H}^+]}\)

\(c = \frac{c_{NH_3}}{M_{NH_3}}, \quad f_{NH_3} = \frac{K_a}{[\text{H}^+] + K_a}\)

\(c_{req} = \left(\frac{K_w}{[\text{H}^+]_t} - [\text{H}^+]_t\right) \frac{[\text{H}^+]_t + K_a}{[\text{H}^+]_t}\, M_{NH_3}\)

Variables

Symbol Meaning SI unit
\(c_{NH_3}\) Ammonia in the water, as NH₃ kg/m³
\(pH_t\) Target pH at 25 °C -
\(pH\) pH at 25 °C from the dose -
\(f_{NH_3}\) Share of the ammonia present as free NH₃ -
\(c_{req}\) Ammonia needed for the target pH, as NH₃ kg/m³
\(pK_a\) pKa of ammonium at 25 °C -
\(K_a\) Dissociation constant of ammonium mol/L
\(K_w\) Ionic product of water at 25 °C (mol/L)²
\(c\) Ammonia concentration mol/L
\(M_{NH_3}\) Molar mass of ammonia kg/kmol
\([\text{H}^+]_t\) Hydrogen ion concentration at the target pH mol/L

Method and standards

The ammonium–ammonia equilibrium constant comes from the Emerson et al. (1975) fit to Bates and Pinching's measurements. The charge balance of pure water with ammonia is solved for the hydrogen ion concentration; the dose for a target pH follows from the same balance in closed form.

Where it is used

  • All-volatile treatment of feedwater (AVT).
  • Setting an ammonia dosing pump rate.
  • Checking condensate pH after ammonia carry-over.

Common mistakes

  • Mixing mg/L as NH₃ with mg/L as N (N × 1.216 = NH₃).
  • Expecting the same pH at operating temperature.
  • Ignoring carbon dioxide in the water, which lowers the pH.

Assumptions and limits

  • Pure water plus ammonia at 25 °C; ideal solution.
  • Kw = 1.0 × 10⁻¹⁴ (the shared water-chemistry value; the 25 °C value is nearer 1.008 × 10⁻¹⁴, a pH difference of about 0.002–0.004).

References

  • Emerson et al. (1975)
  • J. Fish. Res. Board Can. 32
  • ammonium pKa
  • Bates and Pinching (1949)
  • ammonium dissociation

Questions and answers

What pH does 0.5 mg/L of ammonia give?

In pure water at 25 °C, pH 9.19; about 47 % of the ammonia is then free NH₃ and the rest ammonium.

How much ammonia gives pH 9.3?

About 0.72 mg/L as NH₃. pH rises slowly with dose because ammonia is a weak base: each 0.1 pH costs more ammonia.

Why at 25 °C only?

Feedwater pH is measured on a cooled sample at 25 °C; at feedwater temperature the same water has a lower pH because water and ammonium both dissociate more.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.