Nitrogen for Boiler Lay-Up (Dry Storage)

Nitrogen in normal cubic metres to fill a drained boiler at a capping pressure and temperature, times the number of fills or purges, and the cylinders needed.

Process steam and utilitiesSugar mill and cogenerationDistillery and ethanolBoiler

Inputs

Examples: 80 m3, three fillsSmall boiler

Normal m³ per cylinder.

Results

Purge until the vent oxygen is low before capping; keep a small positive pressure and log it daily.

Each fill or purge is counted as a full boiler volume at the capping pressure. For pressure purges vented to atmosphere each cycle adds only about V(p − p_atm)/p_n, so the total is conservative.

Nitrogen (normal m³ at 0 °C, 1 atm)320.13m³
Cylinders46.000

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 80 m3, three fills. The inputs, in the units selected above:

InputValue
Steam–water volume to fill80.000 m³
Nitrogen capping pressure (absolute)1.5000 bar
Temperature30.000 °C
Fills (including purges)3.0000 -
Nitrogen per cylinder (normal m³)7.0000 m³

Applying the formula below gives:

ResultValue
Nitrogen (normal m³ at 0 °C, 1 atm)320.13 m³
Cylinders46.000

Open this example in the calculator and change any input.

Formula

\(V_n = V \frac{p}{p_n}\frac{T_n}{T} n\)

Variables

Symbol Meaning SI unit
\(V\) Steam–water volume to fill m³
\(p\) Nitrogen capping pressure (absolute) Pa
\(T\) Temperature K
\(n\) Fills (including purges) -
\(V_c\) Nitrogen per cylinder (normal m³) m³
\(V_n\) Nitrogen (normal m³ at 0 °C, 1 atm) m³
\(N_c\) Cylinders -

Method and standards

Ideal gas.

Where it is used

  • Off-season preservation.
  • Long outages.

Common mistakes

  • Gauge pressure used as absolute.

Assumptions and limits

  • Ideal gas.
  • Each fill or purge counts as a full boiler volume of nitrogen at the absolute capping pressure (displacement purging). Pressure purges vented to atmosphere use only about V(p − p_atm)/p_n per cycle, so the result is conservative for them (about 3 times high at 1.5 bar absolute).
  • Volumes are normal cubic metres at 0 °C and 1 atm, shown in m³ in every unit system; US standard cubic feet at 60 °F are a different basis.

References

  • Ideal gas V_n = V (p/p_n)(T_n/T) n

Questions and answers

When to lay up with nitrogen?

For off-season sugar and distillery boilers standing for weeks or months.

Wet or dry lay-up?

Wet lay-up with chemicals for short stops; dry with nitrogen or desiccant for long ones.

Why several fills?

Purging displaces air step by step before the final capping fill.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.