FireCADCalc

Water Hardness and TDS Conversions (ppm, °dH, °fH, gpg)

Total hardness as CaCO₃ from calcium and magnesium, in mg/L, German and French degrees, grains per gallon, mmol/L and meq/L, with TDS from conductivity.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserWater treatment plantBoiler attendant and boiler operator examinations

Inputs

Examples: Ca 60 mg/L, Mg 20 mg/L, 600 µS/cmSoft water: Ca 8, Mg 2, 120 µS/cmHard borewell: Ca 150, Mg 60, 1800 µS/cm, k 0.7

Depends on the dissolved salts; calibrate against a gravimetric TDS of your water.

Results

Total hardness, as CaCO₃621.67mg/L
German degrees34.831
French degrees62.167
Grains per US gallon, as CaCO₃36.316
Hardness6.2113mmol/L
Hardness, meq/L12.423
Total dissolved solids (estimate)1,260.0mg/L

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Ca 60 mg/L, Mg 20 mg/L, 600 µS/cm. The inputs, in the units selected above:

InputValue
Calcium, as Ca60.000 mg/L
Magnesium, as Mg20.000 mg/L
Electrical conductivity at 25 °C, µS/cm600.00 -
TDS factor, mg/L per µS/cm0.65000 -

Applying the formula below gives:

ResultValue
Total hardness, as CaCO₃232.20 mg/L
German degrees13.010
French degrees23.220
Grains per US gallon, as CaCO₃13.564
Hardness2.3200 mmol/L
Hardness, meq/L4.6399
Total dissolved solids (estimate)390.00 mg/L

Open this example in the calculator and change any input.

Formula

\(TH = Ca\,\frac{M_{CaCO_3}}{M_{Ca}} + Mg\,\frac{M_{CaCO_3}}{M_{Mg}}\)

\(°dH = \frac{TH}{10\ \text{mg/L}\cdot M_{CaCO_3}/M_{CaO}} \qquad °fH = \frac{TH}{10\ \text{mg/L}} \qquad gpg = \frac{TH}{\text{grain}/\text{US gal}} \qquad c = \frac{TH}{M_{CaCO_3}}\ (\text{mmol/L with } TH \text{ in mg/L and } M \text{ in g/mol}), \quad c_{eq} = 2c \qquad TDS = k \cdot EC\)

Variables

Symbol Meaning SI unit
\(Ca\) calcium, as Ca kg/m³
\(Mg\) magnesium, as Mg kg/m³
\(EC\) electrical conductivity µS/cm
\(k\) TDS factor mg/L per µS/cm
\(TH\) total hardness as CaCO₃ kg/m³
\(°dH\) German degrees –
\(°fH\) French degrees –
\(gpg\) grains per US gallon –
\(c\) hardness in mmol/L –
\(c_{eq}\) hardness in meq/L, \(2c\) –
\(TDS\) total dissolved solids estimate kg/m³
\(M\) molar masses from IUPAC atomic weights kg/kmol

Method and standards

Equivalent conversion to CaCO₃ with IUPAC 2013 atomic weights; unit definitions of the German and French degrees, the grain (64.79891 mg) and the US gallon (231 in³).

Where it is used

  • Reading water analyses from labs that use different units.
  • Softener and DM plant sizing.
  • Setting boiler water and cooling water limits.

Common mistakes

  • Adding Ca and Mg in mg/L directly without converting to CaCO₃.
  • Mixing US and imperial gallons in grains per gallon.
  • Using a TDS factor from another water.

Assumptions and limits

  • Hardness from calcium and magnesium only; TDS is an estimate from conductivity.
  • Conductivity is taken as the value at 25 °C (temperature-compensated). The linear TDS factor suits dilute waters; a note appears above 10 000 µS/cm.

References

  • Hardness unit definitions (°dH = 10 mg/L CaO, °fH = 10 mg/L CaCO3, grain = 64.79891 mg)
  • IUPAC 2013 atomic weights

Questions and answers

How do I convert calcium and magnesium to hardness as CaCO₃?

Multiply calcium by 100.09/40.08 = 2.497 and magnesium by 100.09/24.31 = 4.118. 60 mg/L Ca and 20 mg/L Mg give 232 mg/L as CaCO₃: 13.0 °dH, 23.2 °fH, 13.6 grains per US gallon, 2.32 mmol/L.

How accurate is TDS from conductivity?

Only as good as the factor, which depends on the salts. 0.55–0.7 mg/L per µS/cm is typical; calibrate it against a gravimetric TDS of your own water.

What is the difference between °dH and °fH?

German degrees count CaO (10 mg/L per degree); French degrees count CaCO₃ (10 mg/L per degree). One °dH is 1.785 °fH.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.