Worked example
Example: 3.5 mg on 12 cm2. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Deposit removed from the sample | 3.5000 mg |
| Sample waterside area | 12.000 cm² |
| Deposit density (magnetite about 5000) | 5,000.0 kg/m³ |
| Total waterside area of the circuit | 800.00 m² |
Applying the formula below gives:
| Result | Value |
|---|---|
| Deposit weight density | 2.9167 g/m² |
| Equivalent thickness | 0.58333 µm |
| Total deposit in the circuit | 2.3333 kg |
Open this example in the calculator and change any input.
Formula
\(g_d = \frac{m_s}{A_s}, \quad \delta = \frac{g_d}{\rho_d}, \quad M_d = g_d A_t\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(m_s\) | Deposit removed from the sample | kg |
| \(A_s\) | Sample waterside area | m² |
| \(\rho_d\) | Deposit density (magnetite about 5000) | kg/m³ |
| \(A_t\) | Total waterside area of the circuit | m² |
| \(g_d\) | Deposit weight density | kg/m² |
| \(\delta\) | Equivalent thickness | m |
| \(M_d\) | Total deposit in the circuit | kg |
Method and standards
Definitions.
Where it is used
- Chemical cleaning decisions.
- Acid quantity input.
Common mistakes
- Sample area of the whole circumference used.
Assumptions and limits
- Uniform deposit.
- The total applies the sample's weight density to the whole waterside area. Taken from the heaviest (hot) side, it overstates the circuit total; use it as an upper bound.
References
- Definitions: weight density = mass/area; thickness = weight density/density
Questions and answers
Why weight density?
It is the usual measure for deciding when to chemically clean a boiler.
Which side of the tube?
The hot side (fireside-facing waterside) carries the heaviest deposit: sample there.
Thickness from weight?
Divide by deposit density; porous deposits are thicker than this.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.