FireCADCalc

Tube Deposit Weight Density and Thickness

Deposit weight density from a scraped tube sample, the equivalent deposit thickness and the total deposit on the waterside area, for chemical cleaning decisions.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolBoiler

Inputs

Examples: 3.5 mg on 12 cm2Heavy deposit

Results

Weight density thresholds for cleaning depend on pressure and heat flux; follow your boiler maker's or utility guideline.

Deposit weight density2.9167g/m²
Equivalent thickness0.58333µm
Total deposit in the circuit2.3333kg

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 3.5 mg on 12 cm2. The inputs, in the units selected above:

InputValue
Deposit removed from the sample3.5000 mg
Sample waterside area12.000 cm²
Deposit density (magnetite about 5000)5,000.0 kg/m³
Total waterside area of the circuit800.00 m²

Applying the formula below gives:

ResultValue
Deposit weight density2.9167 g/m²
Equivalent thickness0.58333 µm
Total deposit in the circuit2.3333 kg

Open this example in the calculator and change any input.

Formula

\(g_d = \frac{m_s}{A_s}, \quad \delta = \frac{g_d}{\rho_d}, \quad M_d = g_d A_t\)

Variables

Symbol Meaning SI unit
\(m_s\) Deposit removed from the sample kg
\(A_s\) Sample waterside area m²
\(\rho_d\) Deposit density (magnetite about 5000) kg/m³
\(A_t\) Total waterside area of the circuit m²
\(g_d\) Deposit weight density kg/m²
\(\delta\) Equivalent thickness m
\(M_d\) Total deposit in the circuit kg

Method and standards

Definitions.

Where it is used

  • Chemical cleaning decisions.
  • Acid quantity input.

Common mistakes

  • Sample area of the whole circumference used.

Assumptions and limits

  • Uniform deposit.
  • The total applies the sample's weight density to the whole waterside area. Taken from the heaviest (hot) side, it overstates the circuit total; use it as an upper bound.

References

  • Definitions: weight density = mass/area; thickness = weight density/density

Questions and answers

Why weight density?

It is the usual measure for deciding when to chemically clean a boiler.

Which side of the tube?

The hot side (fireside-facing waterside) carries the heaviest deposit: sample there.

Thickness from weight?

Divide by deposit density; porous deposits are thicker than this.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.