Worked example
Example: 20 t/h, 4 % blowdown, 10 ppm active, 35 % product, 120/kg. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Steam output | 20.000 t/h |
| Blowdown, share of feedwater | 4.0000 % |
| Dose of active chemical in feedwater | 10.000 mg/L |
| Active content of the product as supplied | 35.000 % |
| Price per kg of product (your currency) | 120.00 - |
| Operating hours per year | 8,000.0 h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Product used per day (at full output) | 14.286 kg |
| Cost per tonne of steam (your currency) | 3.5714 |
| Cost per year (your currency) | 571,429 |
| Feedwater flow | 20.833 t/h |
Open this example in the calculator and change any input.
Formula
\(\dot m_{fw} = \frac{\dot m_s}{1 - b} \qquad \dot m_p = \frac{\dot m_{fw}\,c}{\rho_w\,s} \qquad m_d = 86\,400\,\dot m_p \qquad c_t = \frac{\dot m_p\,c_p}{\dot m_s}\cdot 1000\ \mathrm{kg/t} \qquad C_y = \dot m_p\,t_y\,c_p\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_s\) | steam output | kg/s |
| \(b\) | blowdown share of feed | – |
| \(c\) | active dose | kg/m³ |
| \(s\) | active content of product | – |
| \(c_p\) | price per kg | currency |
| \(t_y\) | hours per year | s |
| \(m_d\) | product per day | kg |
| \(c_t\) | cost per tonne of steam | currency |
| \(C_y\) | cost per year | currency |
| \(\dot m_{fw}\) | feedwater flow | kg/s |
| \(\dot m_p\) | product flow | kg/s |
| \(\rho_w\) | 1000 kg/m³ (mg/L taken as mg/kg) | kg/m³ |
Method and standards
Mass balance: dose on feedwater flow, product flow from the active content.
Where it is used
- Treatment programme budgets.
- Comparing chemical suppliers.
- Steam cost build-up.
Common mistakes
- Dosing on steam flow.
- Using product dose as active dose.
- Ignoring condensate return quality.
Assumptions and limits
- Constant dose; full output.
- The dose is on the whole feedwater. Chemicals dosed to the drum (phosphate, for example) are often specified as a boiler-water residual instead: convert that to a feedwater dose (residual × blowdown share of feedwater) first.
References
- Mass balance on feedwater (ppm = mg/kg)
Questions and answers
What does a 10 ppm dose cost on 20 t/h with 4 % blowdown?
With a 35 % product at 120 per kg: 14.3 kg of product a day, 3.57 per tonne of steam, 571 000 a year at 8000 h.
Why use feedwater, not steam?
Chemicals go into the feedwater, which is steam plus blowdown.
Is mg/L the same as ppm?
For dilute water, yes: 1 mg/L ≈ 1 mg/kg.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.